EasyManuals Logo
Home>Danfoss>DC Drives>5000 Flux

Danfoss 5000 Flux User Manual

Danfoss 5000 Flux
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
Electrical data
Bookstyle and Compact, Mains supply 3 x 200 -
240 V
According to international requirements VLT type 5001 5002 5003 5004 5005 5006
Output current
I
VLT,N
[A]
3.7 5.4 7.8 10.6 12.5 15.2
I
VLT, MAX
(60 s) [A]
5.9 8.6 12.5 17 20 24.3
Output (240 V) S
VLT,N
[kVA]
1.5 2.2 3.2 4.4 5.2 6.3
Typical shaft output
P
VLT,N
[kW]
0.75 1.1 1.5 2.2 3.0 3.7
Typical shaft output
P
VLT,N
[HP]
1 1.5 2 3 4 5
Max. cable cross-section to motor,
brake and loadsharing [mm
2
]/[AWG]
2
)
4/10
4/10 4/10 4/10 4/10 4/10
Rated input current
(200 V)I
L,N
[A]
3.4 4.8 7.1 9.5 11.5 14.5
Max. cable
cross-section power [mm
2
]/[AWG]
2
)
4/10
4/10 4/10 4/10 4/10 4/10
Max. pre-fuses
[-]/UL
1)
[A]
16/10 16/10 16/15 25/20 25/25 35/30
Efficiency
3)
0.95 0.95 0.95 0.95 0.95 0.95
Weight IP 20 EB Bookstyle [kg] 7 7 7 9 9 9.5
Weight IP 20 EB Compact [kg] 8 8 8 10 10 10
Weight IP 54 Compact [kg] 11.5 11.5 11.5 13.5 13.5 13.5
Power loss at
max. load.
[W] 58 76 95 126 172 194
Enclosure
IP 20/
IP54
IP 20/
IP54
IP 20/
IP54
IP 20/
IP54
IP 20/
IP54
IP 20/
IP54
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 13
Technical data

Table of Contents

Other manuals for Danfoss 5000 Flux

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss 5000 Flux and is the answer not in the manual?

Danfoss 5000 Flux Specifications

General IconGeneral
BrandDanfoss
Model5000 Flux
CategoryDC Drives
LanguageEnglish

Related product manuals