EasyManuals Logo
Home>Danfoss>Control Unit>CVP

Danfoss CVP User Manual

Danfoss CVP
2 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #2 background imageLoading...
Page #2 background image
© Danfoss | DCS (MWA) | 2017.03
DKRCI.PI.HN0.P3.02 | 520H10898 | 2
Range Range Factory setting 1 Rev (360°) ~
-0.66 7 bar 19.5 in Hg 102 psig ~ 0.8 bar/11.6 psig 1 bar/ 14.5 psig
4 28 bar 58 406 psig ~ 12 bar/174 psig 3.1 bar/ 45 psig
25 52 bar 363 754 psig ~ 26.6 bar/386 psig 4.1 bar/ 59.5 psig
CVP
Range Range Factory setting 1 Rev (360°) ~
-0.66 7 bar 19.5 in Hg 102 psig ~ 0.7 bar/10.2 psig 1 bar/ 14.5 psig
4 28 bar 58 406 psig ~ 7.6 bar/110 psig 3.1 bar/ 45 psig
CVPP
Range Range Factory setting 1 Rev (360°) ~
-0.66 7 bar 19.5 in Hg 102 psig ~ 0.8 bar/11.6 psig 1 bar/ 14.5 psig
4 28 bar 58 406 psig ~ 12 bar/174 psig 3.1 bar/ 45 psig
CVC
Open Close
See installation guide
DKRCI.PI.HV0.K
CVE
-1
0
1
2
3
4
5
6
7
8
0% 20%40% 60%80% 100%
Non-setting area*
Non-setting area*
barg
0
14.5
29.0
43.5
58.0
72.5
87.0
101.5
psig
116.0
-29.5 in. Hg
ICAD reading (spring decompression)
barg -0.66 0 1 2 3 4 5 6 7 8
psig 19.5 in. Hg 0 14.5 29.0 43.5 58.0 72.5 87.0 101.5 116. 0
mA 18.3 17.1 15.9 14.7 13.5 12.3 11.1 9.9 8.7 7.5
ICAD reading % 90% 83% 75% 67% 60% 53% 45% 37% 30% 23%
CVE Pressure setting (see DKRCI.PI.HVO.J for ICAD setup)
* These areas are dedicated regulation band for the pilot. It is recommended not
to exceed the limits in above table
Valve sealingPacking gland leak tightening
(CVP, CVPP & CVC)
Max.
20 Nm (15 ft-lbs)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss CVP and is the answer not in the manual?

Danfoss CVP Specifications

General IconGeneral
BrandDanfoss
ModelCVP
CategoryControl Unit
LanguageEnglish

Related product manuals