EasyManuals Logo
Home>Danfoss>Heat Pump>DHP-AQ Maxi

Danfoss DHP-AQ Maxi User Manual

Danfoss DHP-AQ Maxi
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
°C Outdoor / Defrost sensor
150 ohm, Ω
PT1000 sensor
1000 ohm, Ω
Other sensors
22 kilo ohm, kΩ
-20 1115
-15 868
-10 681
-5 538
0 428 1000 66,3
5 343 52,4
10 276 1039 41,8
15 224 33,5
20 183 1078 27,1
25 150 22,0
30 124 1117 18,0
35 103 14,8
40 86 1155 12,2
45 10,1
50 1194 8,5
55 7,1
60 1232 6,0
65 5,0
70 1271 4,2
75 3,7
80 3,1
85 2,7
3.3.1 Measurement checking sensors during fault tracing
1. Disconnect the relevant sensor from I/O-card/terminal block.
2. Measure the resistance for the sensor and any extension cables.
3. Then measure the sensor only.
N
To ensure the sensor value the actual temperature must be checked against the measured resistance.
Service Instructions DHP-AQ
Danfoss Heating Solutions VMGFJ202
13

Other manuals for Danfoss DHP-AQ Maxi

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss DHP-AQ Maxi and is the answer not in the manual?

Danfoss DHP-AQ Maxi Specifications

General IconGeneral
BrandDanfoss
ModelDHP-AQ Maxi
CategoryHeat Pump
LanguageEnglish

Related product manuals