EasyManuals Logo
Home>Danfoss>Heat Pump>DHP-AQ Maxi

Danfoss DHP-AQ Maxi User Manual

Danfoss DHP-AQ Maxi
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
3.3.2 Positioning sensors
Heat pump
7
8
9
DHP-AQ Maxi
7
DHP-AQ Midi
1. DISCHARGE PIPE SENSOR
2. SUCTION TEMP SENSOR
3. REFR.1 SENSOR
4. REFR.2 SENSOR
5. DEFROST SENSOR (located to rear beside air intake)
6. OUTDOOR SENSOR (positioned on wall to north)
7. SUPPLY LINE SENSOR
8. HOT WATER TOP
9. HOT WATER SENSOR
RETURN LINE SENSOR - Located on return pipe that runs to heat pump. See sys-
tem solution in the Installation instructions.
3.4 Check points
Temperatures
Condensing temperature: 0.5 – 1.5 °C above supply line temperature
Evaporation temperature: 7 - 8 °C
Radiator circuit: 8°K temperature difference
Overheating R407C: 4K ±1 K
Service Instructions DHP-AQ
VMGFJ202 Danfoss Heating Solutions
14

Other manuals for Danfoss DHP-AQ Maxi

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss DHP-AQ Maxi and is the answer not in the manual?

Danfoss DHP-AQ Maxi Specifications

General IconGeneral
BrandDanfoss
ModelDHP-AQ Maxi
CategoryHeat Pump
LanguageEnglish

Related product manuals