MENU>Settings>Flow(boiler)temperature
DesiredT(Desiredflowtemperature)
1x004
WhentheECLComfortisinoverridemode,type"Const.T",thedesiredflow
temperaturecanbeset.
A"Const.T"relatedreturntemperaturelimitationcanalsobeset.SeeMENU
>Settings>Returnlimit>'Con.T,ret.Tlim. '
SeeAppendix“ParameterIDoverview”
Overridemode
WhenECLComfortisinScheduledmode,acontact(switch)signalcan
beappliedtoaninputinordertooverridetoComfort,Saving,Frost
ProtectionorConstanttemperature.Aslongasthecontact(switch)
signalisapplied,theoverrideisactive.
The"DesiredT"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
MENU>Settings>Flow(boiler)temperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.duct/flow/inlettemperatureforthesystem.The
desiredduct/flow/inlettemperaturewillnotbelowerthanthis
setting.Adjustthefactorysetting,ifrequired.
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor
'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn
temperaturelimitation(see'Priority').
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
MENU>Settings>Flow(boiler)temperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flow/duct/inlettemperatureforthesystem.The
desiredtemperaturewillnotbehigherthanthissetting.Adjust
thefactorysetting,ifrequired.
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .