MENU>Settings>Optimization
Boost
1x012
Shortenstheheating-upperiodbyincreasingthedesiredflowtemperature
bythepercentageyouset.
SeeAppendix“ParameterIDoverview
OFF:
Theboostfunctionisnotactive.
Value:
Thedesiredflowtemperatureisincreasedtemporarily
withthesetpercentage.
Inordertoshortentheheating-upperiodafterasaving
temperatureperiod,thedesiredflowtemperaturecanbeincreased
temporarily(max.1hour).Atoptimizingtheboostisactiveinthe
optimizationperiod('Optimizer').
IfaroomtemperaturesensororanECA30/31isconnected,the
booststopswhentheroomtemperatureisreached.
MENU>Settings>Optimization
Ramp(referenceramping)
1x013
Thetime(minutes)inwhichthedesiredflowtemperatureincreases
graduallytoavoidloadpeaksintheheatsupply.
SeeAppendix“ParameterIDoverview
OFF:
Therampingfunctionisnotactive.
Value:
Thedesiredflowtemperatureisincreasedgraduallywith
thesetminutes.
Inordertoavoidloadpeaksinthesupplynetwork,theflow
temperaturecanbesettoincreasegraduallyafteraperiodwith
savingtemperature.Thiscausesthevalvetoopengradually.
X
=
Time
Y
=
Desiredflowtemperature
#1#
=
Rampingtime
=
Comforttemperature
=
Savingtemperature
VI.GU.L2.02
©Danfoss|2017.09|123
OperatingGuideECLComfort210/296/310,applicationA275/A375

Other manuals for Danfoss ECL Comfort A368

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort A368 and is the answer not in the manual?

Danfoss ECL Comfort A368 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort A368
CategoryController
LanguageEnglish

Related product manuals