4 Instructions RI8KL45J © Danfoss 08/2010 EKC 202A, B, C
Clock - Setting of date t45 1 31 1
Clock - Setting of month t46 1 12 1
Clock - Setting of year t47 0 99 0
Miscellaneous
Delay of output signals after start-up o01 0 s 600 s 5 s
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm
when open. 4=defrost start (pulse-pressure). 5=ext.main switch. 6=night operation
7=change reference (activate r40). 8=alarm function when closed. 9=alarm function
when open. 10=case cleaning (pulse pressure). 11=Inject off when open.
o02 0 11 0
Network address o03 0 119 0
On/Off switch (Service Pin message) o04 OFF ON OFF
Access code 1 (all settings) o05 0 100 0
Used sensor type (Pt /PTC/NTC) o06 Pt ntc Pt
Display step = 0.5 (normal 0.1 at Pt sensor) o15 no yes no
Max hold time after coordinated defrost o16 0 min 60 min 20
Configuration of light function (relay 4)
1=ON during day operation. 2=ON / OFF via data communication. 3=ON follows the DI-
function, when DI is selected to door function or to door alarm
o38 1 3 1
Activation of light relay (only if o38=2) o39 OFF ON OFF
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off. o46 0 2 0
Access code 2 (partly access) o64 0 100 0
Save the controllers present settings to the programming key. Select your own number. o65 0 25 0
Load a set of settings from the programming key (previously saved via o65 function) o66 0 25 0
Replace the controllers factory settings with the present settings o67 OFF On OFF
Select application for S5 sensor (0=defrost sensor, 1= product sensor, 2=condenser sen-
sor with alarm)
o70 0 2 0
Select application for relay 4: 1=defrost/light, 2= alarm o72 defrost /
Alarm
Light /
Alarm
1 2 2
Service
Temperature measured with S5 sensor u09
Status on DI1 input. on/1=closed u10
Status on night operation (on or off) 1=closed u13
Read the present regulation reference u28
Status on relay for cooling (Can be controlled manually, but only when r12=-1) u58
Status on relay for fans (Can be controlled manually, but only when r12=-1) u59
Status on relay for defrost. (Can be controlled manually, but only when r12=-1) u60
Temperature measured with Sair sensor u69
Status on relay 4 (alarm, defrost, light).(Can be controlled manually, but only when
r12=-1)
u71
Fault code display Alarm code display Status code display
E1 Fault in controller A 1 High temperature alarm S0 Regulating
E6 Change battery + check clock A 2 Low temperature alarm S1 Waiting for end of the coordinated defrost
E 27 S5 sensor error A 4 Door alarm S2 ON-time Compressor
E 29 Sair sensor error A 5 Max. Hold time S3 OFF-time Compressor
A 15 DI 1 alarm S4 Drip-off time
A 45 Standby mode S10 Refrigeration stopped by main switch
A 59 Case cleasning S11 Refrigeration stopped by thermostat
A 61 Condenser alarm S14 Defrost sequence. Defrosting
S15 Defrost sequence. Fan delay
S16 Refrigeration stopped. (open DI input)
S17 Door open (open DI input)
S20 Emergency cooling
S25 Manual control of outputs
S29 Case cleaning
S32 Delay of output at start-up
non The defrost temperature cannot be dis-
played. There is stop based on time
-d- Defrost in progress / First cooling after
defrost
PS Password required. Set password
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you recon nect the supply voltage

Other manuals for Danfoss EKC 202A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKC 202A and is the answer not in the manual?

Danfoss EKC 202A Specifications

General IconGeneral
BrandDanfoss
ModelEKC 202A
CategoryController
LanguageEnglish

Related product manuals