User manual ERC 113 refrigeration controller
"oEn" OEM code Middle
"oEH" OEM code High
"PAr" Parameter version
OEM parameter version number [requires EKA copy key update].
"CHd" Manufacturing date
Programme date WWY: week number and year number (2010-19).
"SFC" Set as Default
Resets all parameters to last good OEM settings.
"Ctt" Condenser Temp
Temperature of the condensor sensor.
"Et1" Evaporator1 Temp
Temperature of the evaporator sensor1.
"Et2" Evaporator2 Temp
Temperature of the evaporator sensor2.
"AuS" AUX Temp.
Temperature of the AUX sensor. invisible.
"LLu" Light level value
Actual light level value from light sensor.
"Pir" Motion sensor state
"att" Raw Sair Temp
"ESS" External ECO switch state
Display messages
"unP" Device is unprogrammed (relay output is lockt)
"Prg" Device has not finished programming (relay output is lockt)
"Eco" Device is in Eco mode
"SC" Device is in pull-down mode (super-chill)
"dEF" Device is defrosting
"HoL" Device is in Holiday mode
Produced by Danfoss A/S (ADAP-KOOL®) | 2016-07