Parameter name - ERC 211 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5
Relay 1 counter
(1 count=100 cycles of
operation)
o23 0 999 0 0 0 0 0 -
Predened applications o61 AP0 AP5 AP0 AP1 AP2 AP3 AP4 -
Save settings as factory
WARNING: the earlier factory
settings are overwritten
o67 no yES no no no no no -
Display at defrost
Air=actual air temperature,
FrE=freezed temperature,
-d-="-d-" is displayed
o91 Air -d- -d- - -d- -d- - -d-
Polarity P--
DI1 input polarity
nc=normally closed,
no=normally open
P73 nc no no no no no no no
Keyboard lock enable P76 no yES no no no no no -
Readouts u--
Controller status
S0=cooling ON/Heating ON,
S2=wait for compressor ON time
to elapse,
S3=wait for compressor OFF time
to elapse-restart time,
S4=drip OFF delay after defrost,
S10=cooling stop
S11=cooling stopped by
thermostat/heating OFF,
S14=defrosting state,
S15=fan delay state after defrost,
S17=door open (DI input),
S20=emergency cooling,
S25=manual control of outputs,
S30=continous cycle/Pull-down,
S32=delay of outputs at power up
u00 S0 S32 --
Air temperature (Sair) u01 -100.0 200.0 C/F ---
Read the present regulation
reference
u02 -100.0 200.0 C/F ---
DI1 input u10 oFF on ---
Status of night operation u13 oFF on ---
Condenser temperature (Sc) U09 -100.0 200.0 C/F ---
Compressor relay status u58 oFF on ---
Firmware version readout u80 000 999 ---
Note: hidden parameters are greyed out