Do not measure inside the ICAD itself (value can be checked in ICAD menu)
Supply voltage
24 V DC (Tolerances; see Table 3)
Table 2: Load
ICAD 600B, ICAD 600B-TS
1.2 A
ICAD 1200B
2.0 A
24 Volt DC ONLY
CAUTION:
Please observe cable voltage drop
Please observe cable voltage drop. Distance between the applied DC transformer and the ICAD terminal box may
cause a voltage drop. Cross section of cables and size of DC transformer must be calculated so that the voltage at
all time at the ICAD terminal box
(1)
, both during standstill and during operation of ICAD, is within this range:
Table 3: ICAD Supply voltage tolerances
Prefabricated ICAD cable length Code number
1.5 m
3 m
10 m
15 m
027H0426
027H0438
027H0427
027H0435
Voltage ICAD terminal
(600B/1200B) [V DC]
Min.
21
22
23
24
Max.
26.4
Fail safe supply
24 V DC (Tolerances; see Table 3)
Table 4: Load
ICAD 600B, ICAD 600B-TS
1.2 A
ICAD 1200B
2.0 A
Data communication
RS-485: It is important that the installation of the data communication cable is done correctly. Remember
termination at the bus termination. Max length of cable: 1200 m with specic cable and limited data rate. Follow
RS-485 standard.
Insulation from power supply input, metallic part and interface output: 500 V DC: For input/output connections.
Analog Input - Current or Voltage
Table 5: Current
Input range
0/4 – 20 mA
Max input range
0 – 24 mA
Input resistance
120 Ω + diode voltage 0.7 V DC
Measurement error
<±1.5% of the full scale
Reverse polarity protection
yes
Overcurrent protection
yes
Table 6: Voltage
Input range
0/2 – 10 V DC
Max input range
0 – 12 V DC
Measurement error
<±1.5% of the full scale
Reverse polarity protection
yes
© Danfoss | Climate Solutions | 2024.01 BC465027827472en-000102 | 9
ICM and ICMTS Motorized Valves with ICAD Actuators

Table of Contents

Other manuals for Danfoss ICAD 600B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ICAD 600B and is the answer not in the manual?

Danfoss ICAD 600B Specifications

General IconGeneral
BrandDanfoss
ModelICAD 600B
CategoryControl Unit
LanguageEnglish

Related product manuals