MCD Soft Starter Remote Operator
MG.17.E2.02 – VLT is a registered Danfoss trademark 9
Fault Description
General Faults
Indication Problem/Possible Solution
No display No control supply voltage.
Check that correct voltage is
present at terminals 1 and 2.
AMPS or
TEMP LED
flashing
Soft starter in restart delay mode.
Wait for the restart delay
(programmed in the soft starter) to
elapse.
Four dashes
on display
and RS485
LED flashing
A loss of communication has been
detected on the RS485 link to the soft
starter.
Verify and solve the cause for loss
of communication. If
communication is restored before
the soft starter registers a
Communications Failure, the
display will return to active status
and the RS485 LED will illuminate.
If communication is restored after
the soft starter registers a
Communications Failure, the
display will indicate a trip code.
Use the Reset/- Pushbutton to
reset the soft starter fault.
- Incorrect or no 4-20 mA Analogue
Output signal.
Check the correct voltage is
present at terminals 1 and 2.
Check that correct polarity is used
at terminals B10 and B11.
Check that Motor FLC and
Analogue Output 4 mA Offset
parameters are set correctly.
- The motor cannot be started.
Check that control voltage is
connected to the starter.
If connected to an MCD 200
starter, check that terminals A1
and N2 are linked.