EasyManuals Logo
Home>Danfoss>Temperature Controller>Optyma AK-RC 205C

Danfoss Optyma AK-RC 205C User Manual

Danfoss Optyma AK-RC 205C
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #4 background imageLoading...
Page #4 background image
4 | AN41473467835501-000102
© Danfoss | Climate Solutions | 2022.08
Conguration
Condensed programming menu
Enables the rapid conguration of the most frequently-used parameters (SP, C1, d0, d1, d4, F3, A1 and A2). Press the SET key for 3
seconds to access it.
Extended programming menu
Use the extended programming menu to congure all of the unit’s parameters in order to adapt it to installation requirements. Press the
SET key for 6 seconds to access it.
Regulation and control
Important:
If the function of the password has been congured as a keypad block (b10=2), or as an access block to parameters (b10=1), you
will be requested to enter the access code programmed in PAS when attempting to access either of the two functions. If the entered
password is not correct, the unit will go back to showing the temperature.
Certain parameters or menus may not be visible depending on the conguration of the rest of the parameters.
Level 1 Level 2 Description Values Min. Def. Max.
rE
SP Temperature setting (Set Point) °C/°F -50 0.0 99
C0 Probe 1 calibration (Oset) °C/°F -20.0 0.0 20.0
C1 Probe 1 dierential (Hysteresis) °C/°F 0.1 2.0 20.0
C2 Set Point top locking (it cannot be set above this value) °C/°F C3 99 99
C3 Set Point bottom locking (it cannot be set below this value) °C/°F -50 -50 C2
C4
Type of delay for the protection of the compressor:
0=Minimum time of compressor in OFF
1=Minimum time of compressor in OFF and in ON in each cycle
0 0 1
C5 Protection delay time (Value of the option selected in parameter C4) Min. 0 0 120
C6
COOL relay status with fault in probe 1:
0=OFF; 1=ON; 2=Average according to last 24 h prior to probe error
3=ON-OFF according to prog. C7 and C8
0 2 3
C7
Relay time in ON in the event of probe 1 failure
(If C7=0 and C8≠0, the relay will always be disconnected in OFF)
Min. 0 10 120
C8
Relay time in OFF in the event of probe 1 failure
(If C8=0 and C7≠0, the relay will always be connected in ON)
Min. 0 5 120
C9 Maximum duration of the continuous cycle mode. (0=deactivated) H. 0 0 48
C10
Variation of the Set Point (SP) in continuous cycle mode. When it reaches
this point (SP+C10), it reverts to the normal mode. (SP+C10 ≥ C3).
The value of this parameter is always negative, unless it is 0. (0=OFF)
°C/°F 0 -50 C3-SP
C12
Variation of the Set Point (SP) when the change Set Point function is active.
(SP+C12 ≤ C2) (0= deactivated)
°C/°F C3-SP 0.0 C2-SP
C19
Maximum start time from Pump Down
(Values between 1 and 9 seconds will not be accepted) (0=deactivated)
Sec. 0 0 120
C20 Maximum time for pump down (0= deactivated) Min. 0 0 15
C21
Probe to be displayed: 0=All probes (sequential)
1=Probe 1 (Cold Room), 2=Probe 2 (Evaporator), 3=Probe 3 (According to
I20)
0 1 3
C22 Stop fans and compressor on opening door 0=No, 1=Yes 0 0 1
C23 Start-up delay for fans and compressor with door open Min. 0 0 999
C27 Probe 3 calibration (Oset) °C/°F -20.0 0.0 20.0
EP Exit to level 1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Optyma AK-RC 205C and is the answer not in the manual?

Danfoss Optyma AK-RC 205C Specifications

General IconGeneral
BrandDanfoss
ModelOptyma AK-RC 205C
CategoryTemperature Controller
LanguageEnglish

Related product manuals