To setPress “ ” button for 3 seconds till “ ” display, there’s a number of count down in the center of LCD, Use “ ” or
” to adjust the desired sleep time: the max. = 48 hours; thermostat will return to the working status after 5
seconds, “ ” is flashing to start counting down. The setpoint should be replaced by the sleep setpoint.
To quit: When thermostat get into Sleep function, “
” will flash, press “ ” or “ ” to quit.
" Keypad lock: press “ ” and “ ” for 10 seconds till to “ ” display to activate, under this function, any keypad is locked.
Press “ ” and “ ” for 10 seconds till “ ” disappear to quit the function.
" Set Parameters: With thermostat off, press “
” for 10 seconds to enter menu to set the parameters.
Parameter table
Paramete Description Default Range Step
1 Power on status (0: Off; 1: On; 2: Hold) 2 0 - 2
2 Fan speed (0: Single Speed; 1: Three Speed) 1 0 - 1
3 Fan mode (DA; DB) 0
4 Sensor selection (0: Internal; 1: Remote) 1 0 - 1
5 Temperature format (0: Celsius; 1: Fahrenheit) 0 0 - 1 0.1
6 Temperature calibration 0 -20.0 -20.0 0.1
7 Minimum setpoint 5/41 0 - 99.5 0.5
8 Maximum setpoint 35/96 0 - 99.5 0.5
9 Dead band (REPI-4) 2 0 - 10 0.5
10 Heating & Auto sleep setpoint 7/45 0 - 99.5 0.5
11 Cooling sleep setpoint 28/82 0 - 99.5 0.5
12 Comms# (REPI-2N;REPI-4N) 1 1 - 32 1
13
Input Signal Mode
0: Invalid
1: Changeover(REPI-2)
2: thermostat will be sleep without input signal
3: thermostat will be Off without input signal
0 0 - 3
14 Heating reset time 90 sec. 10 - 300 sec. 10 sec.
15 Cooling reset time 90 sec. 10 - 300 sec. 10 sec.
16 Ports mode (0: Modulation & Floating; 1: On/Off) 0 0 - 1
17 Valve status as turn off (0: Close; 1:Hold; 2: Open ) 0 0 - 2
18 Port1 Modulation direction(0:10V Open; 1:10V Close) 0 0 - 1
19 Port1 Modulation minimum signal 0Bit 0-128Bit(5V/10mA) 0.04V/Bit(0.08mA/Bit)
20 Port1 Modulation proportional 2 1 - 20 0.5
21 Port2 Modulation direction(0:10V Open;1:10V Close) 0 0 - 1
22 Port2 Modulation minimum Signal 0 Bit 0-128Bit(5V/10mA) 0.04V/Bit(0.08mA/Bit)
23 Port2 Modulation proportional 2 1 - 20 0.5
24 Port1 Floating minimum time 1 sec. 1 - 9 sec. 1 sec.
25 Port1 Floating maximum time 30 sec. 10 - 300 sec. 10 sec.
26 Port1 Floating minimum time 1 sec. 1-9 sec. 1 sec.
27 Port1 Floating maximum time 30 sec. 10 - 300 sec. 10 sec.
28
Disable / Enable bypass PID control
( 0: Disable; 1: Enable )
0 0 - 1
29
Override output value when bypass PID control
Display output value when enable PID control
0 - 255
30
Override output value when bypass PID control
Display output value when enable PID control
0 - 255

Other manuals for Danfoss REPI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss REPI Series and is the answer not in the manual?

Danfoss REPI Series Specifications

General IconGeneral
BrandDanfoss
ModelREPI Series
CategoryThermostat
LanguageEnglish

Related product manuals