50/60 Hz ground loops
With very long control cables, ground loops may occur. To
eliminate ground loops, connect one end of the screen-to-
ground with a 100 nF capacitor (keeping leads short).
Illustration 3.10 Avoiding Ground Loops
Avoid EMC noise on serial communication
This terminal is connected to ground via an internal RC
link. Use twisted-pair cables to reduce interference
between conductors. The recommended method is shown
below:
1
Min. 16 mm
2
2 Equalizing cable
Illustration 3.11 Avoiding EMC Noise
Alternatively, the connection to terminal 61 can be
omitted:
Illustration 3.13 Control Terminal Locations
•
Connector 1 provides four programmable digital
input terminals, two additional digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage
•
Connector 2 terminals (+)68 and (-)69 are for an
RS485 serial communications connection
•
Connector 3 provides 2 analog inputs, one
analog output, 10 V DC supply voltage, and
commons for the inputs and output
•
Connector 4 is a USB port available for use with
the MCT 10 Set-up Software
•
Also provided are 2 Form C relay outputs that are
located on the power card