Operation & Display
001 Language
(language)
Value:
English (english) [0]
German (deutsch) [1]
French (francais) [2]
Danish (dansk) [3]
Spanish (espanol) [4]
Italian (italiano) [5]
Function:
This parameter is used to choose the language to be
shown in the display whenever the LCP control unit is
connected.
Description of choice:
There is a choice of the languages shown. The factory
setting may vary.
002 Local/remote operation
(OPERATION SITE)
Value:
Remote operation (REMOTE) [0]
Local operation (LOCAL) [1]
Function:
There is a choice of two different modes of operation
of the frequency converter; Remote operation [0] or
Local operation [1]. See also parameter 013 Local con-
trol if Local operation [1] is selected.
Description of choice:
If Remote operation [0] is selected, the frequency con-
verter is controlled via:
1. the control terminals or via serial communi-
cation.
2. the [START] key. This cannot, however,
override stop commands transmitted via the
digital inputs or via serial communication.
3. the [STOP/RESET] and [JOG] keys, on the
condition that these are active.
If Local operation [1], is selected, the frequency con-
verter is controlled via:
1. the [START] key. This cannot, however,
override stop commands via the digital inputs
(see parameter 013 Local control).
2. the [STOP/RESET] and [JOG] keys, on the
condition that these are active.
3. the [FWD/REV] key, on the condition that is
has been selected as active in parameter 016
Local reversing, and that parameter 013 Local
control is set at Local control and open loop
[1] or Local control as parameter 100 [3]. Pa-
rameter 200 Output frequency range is set
at Both directions.
4.
parameter 003 Local reference where the ref-
erence can be set using the [+] and [-] keys.
5. an external control command that can be
connected to the digital inputs (see parame-
ter 013 Local control).
NB!
The [JOG] and [FWD/REV] keys are lo-
cated on the LCP control unit.
003 Local reference
(LOCAL REFERENCE)
Value:
Par. 013 Local control must be set to [1]
or [2]:
0 - f
MAX
(par. 205)
50 Hz
Par. 013 Local control must be set to [3] or
[4].
Ref
MIN
- Ref
MAX
(par. 204-205)
0,0
Function:
In this parameter, the local reference can be set man-
ually. The unit of the local reference depends on the
configuration selected in parameter 100 Configura-
tion.
Description of choice:
In order to protect the local reference, parameter 002
Local/remote operation must be set to Local opera-
tion [1]. Local reference cannot be set via serial com-
munication.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
10 MG.27.A2.02 - VLT
®
is a registered Danfoss trademark