EasyManuals Logo
Home>Danfoss>DC Drives>VLT 28

Danfoss VLT 28 User Manual

Danfoss VLT 28
103 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #79 background imageLoading...
Page #79 background image
No. Description Warning Alarm Trip
locked
2 Live zero error (LIVE ZERO ERROR) X X X
4 Mains phase loss (MAINS PHASE LOSS) X X X
5 Voltage warning high (DC LINK VOLTAGE HIGH) X
6 Voltage warning low (DC LINK VOLTAGE LOW) X
7 Overvoltage (DC LINK OVERVOLT) X X X
8 Undervoltage (DC LINK UNDERVOLT) X X X
9 Inverter overload (INVERTER TIME) X X
10 Motor overloaded ( MOTOR, TIME) X X
11 Motor thermistor (MOTOR THERMISTOR) X X
12 Current limit (CURRENT LIMIT) X X
13 Overcurrent (OVERCURRENT) X X X
14 Earth fault (EARTH FAULT) X X
15 Switch mode fault (SWITCH MODE FAULT) X X
16 Short-circuit (CURR. SHORT CIRCUIT) X X
17 Serial communication timeout (STD BUS TIMEOUT) X X
18 HPFB bus timeout (HPFB TIMEOUT) X X
33 Out of frequency range (OUT FREQ RNG/ROT LIM) X
34 HPFB communication fault (PROFIBUS OPT. FAULT) X X
35 Inrush fault (INRUSH FAULT) X X
36 Overtemperature (OVERTEMPERATURE) X X
37-45 Internal fault (INTERNAL FAULT) X X
50 AMT not possible X
51 AMT fault re. nameplate data (AMT TYPE.DATA FAULT) X
54 AMT wrong motor (AMT WRONG MOTOR) X
55 AMT timeout (AMT TIMEOUT) X
56 AMT warning during AMT (AMT WARN. DURING AMT) X
99 Locked (LOCKED) X
LED indication
Warning
yellow
Alarm red
Trip locked yellow and red
WARNING/ALARM 2: Live zero fault
The voltage or current signal on terminal 53 or 60 is
below 50% of the preset value in parameter 309 or 315
Terminal, min. scaling.
WARNING/ALARM 4: Mains phase fault
No phase on mains supply side. Check the supply
voltage to the frequency converter. This fault is only
active in 3-phase mains supply. The alarm can also
occur when the load is pulsing. In this instance the
pulses must be dampened, e.g. using an inertia disc.
WARNING 5: Voltage warning high
If the intermediate circuit voltage (UDC) is higher than
Voltage warning high the frequency converter will give
a warning and the motor will continue to run un-
changed. If the UDC remains above the voltage warn-
ing limit, the inverter will trip after a set time. The time
depends on the device, and is set at 5 - 10 sec. Note:
The frequency converter will trip with an alarm 7 (over-
voltage). A voltage warning can occur when the con-
nected mains voltage is too high. Check whether the
supply voltage is suitable for the frequency converter,
see Technical data. A voltage warning can also occur
if the motor frequency is reduced too quickly due to
ramp down time being too short.
WARNING 6: Voltage warning low
If the intermediate circuit voltage (UDC) is lower than
Voltage warning low the frequency converter will give
a warning and the motor will continue to run un-
changed. A voltage warning can occur when the con-
nected mains voltage is too low. Check whether the
supply voltage is suitable for the frequency converter,
see Technical data. When the frequency converter is
switched off a brief warning 6 (and warning 8) appears.
WARNING/ALARM 7: Overvoltage
If the intermediate voltage (UDC) goes over the inver-
ter's Overvoltage limit the inverter will be switched off
until the UDC has once more fallen below the over-
voltage limit. If the UDC remains above the overvoltag
limit the inverter will trip after a set time. The time de-
pends on the device, and is set at 5 - 10 sec. An
VLT
®
2800 Series
78 MG.27.A2.02 - VLT
®
is a registered Danfoss trademark

Other manuals for Danfoss VLT 28

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 28 and is the answer not in the manual?

Danfoss VLT 28 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 28
CategoryDC Drives
LanguageEnglish

Related product manuals