Select Special motor mode [8], if a special U/f setting
is needed that is to be adapted to the present motor.
The break points are set in parameters 423-428 Volt-
age/frequency .
NB!
Please note that if a value set in the name-
plate parameters 102-106 is changed,
there will be an automatic change of pa-
rameter 108 Stator resistance and 109
Stator reactance.
102
Motor power P
M,N
(motor power)
Value:
0.25 - 22 kW
Depends on unit
Function:
Here you must set a power value [kW] P
M,N
, corre-
sponding to the motor's rated power. The factory sets
a rated power value [kW] P
M,N
, that depends on the
type of unit.
Description of choice:
Set a value that matches the nameplate data on the
motor. Settings between one size below and one size
over the factory setting are possible.
103
Motor voltage U
M,N
(MOTOR VOLTAGE)
Value:
For 200 V units: 50 - 999 V
230 V
For 400 V units: 50 - 999 V
400 V
Function:
This is where to set the rated motor voltage U
M,N
for
either star Y or delta .
Description of choice:
Select a value that corresponds to the nameplate data
on the motor, regardless of the frequency converter's
mains voltage.
104
Motor frequency f
M,N
(MOTOR FREQUENCY)
Value:
24-1000 Hz
50 Hz
Function:
This is where to select the rated motor frequency
f
M,N
.
Description of choice:
Select a value that corresponds to the nameplate data
on the motor.
105
Motor current I
M,N
(MOTOR CURRENT)
Value:
0,01 - I
MAX
Depends on choice of motor
Function:
The nominal, rated current of the motor I
M,N
forms part
of the frequency converter calculation of features such
as torque and motor thermal protection.
Description of choice:
Set a value that corresponds to the nameplate data on
the motor. Set the motor current I
M,N
taking into ac-
count whether the motor is star-connected Y or delta-
connected .
106 Rated motor speed
(MOTOR NOM. SPEED)
Value:
100 - f
M,N
x 60 (max.
60000 rpm)
Depends on parame-
ter 104 Motor frequency,
f
M,N
Function:
This is where to set the value that corresponds to the
rated motor speed n
M,N
that can be seen from the
nameplate data.
Description of choice:
Select a value that corresponds to the nameplate data
on the motor.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark 19
Programming

Other manuals for Danfoss VLT 2800 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 Series and is the answer not in the manual?

Danfoss VLT 2800 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800 Series
CategoryDC Drives
LanguageEnglish

Related product manuals