General technical data
Mains supply (L1, L2, L3):
Supply voltage VLT 2803-2840 220-240 V (N, L1) 1 x 220/230/240 V ±10%
Supply voltage VLT 2803-2840 200-240 V 3 x 200/208/220/230/240 V ±10%
Supply voltage VLT 2805-2882 380-480 V 3 x 380/400/415/440/480 V ±10%
Supply voltage VLT 2805-2840 (R5) 380 / 400 V + 10 %
Supply frequency 50/60 Hz ± 3 Hz
Max. imbalance on supply voltage ± 2.0% of rated supply voltage
True Power Factor ()
0.90 nominal at rated load
Displacement Power Factor (cos )
near unity (> 0.98)
Number of connections at supply input L1, L2, L3 2 times/min.
Max. short-circuit value 100,000 A
See Special Conditions section in the Design Guide
Output data (U, V, W):
Output voltage 0 - 100% of supply voltage
Output frequency 0.2 - 132 Hz, 1 - 1000 Hz
Rated motor voltage, 200-240 V units 200/208/220/230/240 V
Rated motor voltage, 380-480 V units 380/400/415/440/460/480 V
Rated motor frequency 50/60 Hz
Switching on output Unlimited
Ramp times 0.02 - 3600 sec.
Torque characteristics:
Starting torque (parameter 101 Torque characteristic = Constant torque) 160% in 1 min.
*
Starting torque (parameter 101 Torque characteristics = Variable torque) 160% in 1 min.
*
Starting torque (parameter 119 High starting torque ) 180% for 0.5 sec.
Overload torque (parameter 101 Torque characteristic = Constant torque) 160%*
Overload torque (parameter 101 Torque characteristic = Variable torque) 160%*
Percentage relates to frequency converter's nominal current.
* VLT 2822 PD2 / 2840 PD2 1 x 220 V only 110% in 1 min.
Control card, digital inputs:
Number of programmable digital inputs 5
Terminal number 18, 19, 27, 29, 33
Voltage level 0 - 24 V DC (PNP positive logic)
Voltage level, logic '0' < 5 V DC
Voltage level, logic '1' > 10 V DC
Maximum voltage on input 28 V DC
Input resistance, R
i
(terminals 18, 19, 27, 29)
approx. 4 k
Input resistance, R
i
(terminal 33)
approx. 2 k
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. See section
entitled Galvanic Isolation.
VLT
®
2800 Series
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark 85
All about VLT 2800

Other manuals for Danfoss VLT 2800 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 Series and is the answer not in the manual?

Danfoss VLT 2800 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800 Series
CategoryDC Drives
LanguageEnglish

Related product manuals