Technical data, mains supply 3 x 380 - 480 V
According to international standards Type 2805 2807 2811 2815 2822 2830
Output current I
INV.
[A] 1.7 2.1 3.0 3.7 5.2 7.0
(3 x 380-480V)
I
MAX
(60s) [A] 2.7 3.3 4.8 5.9 8.3 11.2
Output power (400 V) S
INV.
[KVA] 1.1 1.7 2.0 2.6 3.6 4.8
Typical shaft output P
M,N
[kW] 0.55 0.75 1.1 1.5 2.2 3.0
Typical shaft output P
M,N
[HP] 0.75 1.0 1.5 2.0 3.0 4.0
Max. cable cross section,
motor
[mm
2
/AWG]
1)
4/10 4/10 4/10 4/10 4/10 4/10
Input current I
L,N
[A] 1.6 1.9 2.6 3.2 4.7 6.1
(3 x 380-480 V)
I
L,MAX
(60s)[A] 2.6 3.0 4.2 5.1 7.5 9.8
Max. cable cross section,
power
[mm
2
/AWG]
1)
4/10 4/10 4/10 4/10 4/10 4/10
Max. pre-fuses
IEC/UL
2)
[A]
20/20 20/20 20/20 20/20 20/20 20/20
Efficiency
3)
[%] 96 96 96 96 96 96
Power loss at 100% load [W] 28 38 55 75 110 150
Weight [kg] 2.1 2.1 2.1 2.1 3.7 3.7
Enclosure
4
type IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
According to international standards Type 2840 2855 2875 2880 2881 2882
Output current I
INV.
[A] 9.1 12 16 24 32.0 37.5
(3 x 380-480V)
I
MAX
(60s) [A] 14.5 19.2 25.6 38.4 51.2 60.0
Output power (400 V) S
INV.
[KVA] 6.3 8.3 11.1 16.6 22.2 26.0
Typical shaft output P
M,N
[kW] 4.0 5.5 7.5 11.0 15.0 18.5
Typical shaft output P
M,N
[HP] 5.0 7.5 10.0 15.0 20.0 25.0
Max. cable cross sec-
tion, motor
[mm
2
/AWG]
1)
4/10 4/10 4/10 16/6 16/6 16/6
Input current I
L,N
[A] 8.1 10.6 14.9 24.0 32.0 37.5
(3 x 380-480 V)
I
L,MAX
(60s)[A] 13.0 17.0 23.8 38.4 51.2 60
Max. cable cross sec-
tion, power
[mm
2
/AWG]
1)
4/10 4/10 4/10 16/6 16/6 16/6
Max. pre-fuses
IEC/UL
2)
[A]
20/20 25/25 25/25 50/50 50/50 50/50
Efficiency
3)
[%] 96 96 96 97 97 97
Power loss at 100% load [W] 200 275 372 412 562 693
Weight [kg] 3.7 6.0 6.0 18.5 18.5 18.5
Enclosure
4
type IP20 IP20 IP20 IP20/
NEMA 1
IP20/
NEMA 1
IP20/
NEMA 1
1. American Wire Gauge. Max. cable cross section is
the largest cable cross section that can be attached to
the terminals. Always observe national and local reg-
ulations.
2. Type gG pre-fuses must be used for installation ac-
cording to IEC rules. If you want to maintain UL/cUL
you must use pre-fuses of the type Bussmann KTN-R
200 V, KTS-R 500 V or Ferraz Shawmut, type ATMR
(max. 30A). The fuses must be placed for protection in
a circuit that is capable of supplying a maximum of
100,000 amps RMS (symmetrical), 500 V maximum.
See table under Pre-fuses.
3. Measured using a 25 m screened/armoured motor
cable with a rated load and rated frequency.
4. IP20 is standard for VLT 2805-2875, whereas
NEMA 1 is an option.
VLT
®
2800 Series
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark 91
All about VLT 2800

Other manuals for Danfoss VLT 2805

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2805 and is the answer not in the manual?

Danfoss VLT 2805 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2805
CategoryDC Drives
LanguageEnglish

Related product manuals