Over-temp
The temperature inside the VLT
®
frequency
converter is too high. Possible reasons:
the ambient temperature is too high (max.
40/45 °C), the VLT
®
frequency converter’s
cooling ribs are covered, or the VLT
®
fre-
quency converter's fan is defective.
Reduce the ambient temperature by
increasing the ventilation.
Uncover/clean the cooling ribs.
Replace the fan.
Overload
The electronic VLT
®
protection is active.
This means that the motor has consumed
more than 105% of rated VLT
®
frequency
converter current for too long.
Reduce the motor load. If this is not
possible the application may require a
larger VLT
®
frequency converter.
Motor trip
The electronic motor protection is active.
This means that the current consumed by
the motor at low speed has been too high
for too long.
The motor has been loaded
excessively at low speed.
If the load cannot be changed,
you must exchange the motor for
a bigger one, or provide extra cooling
of the existing motor.
If so, the electronic motor protection
can be de-activated in parameter 315.
Fault messages
Inverter fault
The VLT
®
power section is defective.
Overvoltage
The voltage of the VLT
®
frequency conver-
ter’s intermediate circuit (DC-voltage) is too
high. Possible reasons: line voltage too
high, transients on the line voltage, or re-
generative motor operation.
Note: When the VLT
®
frequency converter
is stopped, repeated transients are charg-
ing the intermediate circuit, as it supplies no
power to the motor.
If the fault indication is given when
the speed is reduced, you can increase
the ramp-down time. If this is not
possible, the application may require a
VLT
®
frequency converter with brake.
If the fault indication is given in other
situations, the problem will be due to
the mains supply.
Undervoltage
The voltage of the VLT
®
frequency conver-
ter’s intermediate circuit (DC-voltage) is too
low. Possible reasons: line voltage too low
or defect in the VLT
®
frequency converter’s
charging circuit/rectifier.
Check whether the line voltage is OK.
Overcurrent
The peak current limit of the inverter has
been reached. This may be due to a short-
circuit in the output of the VLT
®
frequency
converter.
Check the motor and the motor cable
for ground failure.
Ground fault
Ground failure on the VLT
®
frequency con-
verter output. Another reason might be that
the motor cable is too long.
Consult the data sheets for permitted
cable length.
Check the motor and the motor cable
for earth leakage.
Fault messages
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 3002 and is the answer not in the manual?

Danfoss VLT 3002 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 3002
CategoryMedia Converter
LanguageEnglish

Related product manuals