67MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Group description
Load and motors
Group 1..
(continued)
PID optimisation
Parameter 121
(proportional gain) is set for 0.01
(min. value, factory setting).
Parameter 122
(integration time) is set for infinite
(max. value, factory setting).
Parameter 123
(differentiation time) is set for 0 sec.
1. Start the frequency converter.
2. Increase the value in parameter 121
(proportional amplification) until the
feedback signal (FB) oscillates
constantly. Reduce the value until the
oscillation ceases. Reduce further
(0.4-0.6 times).
3. Reduce the value in parameter 122
(integration time) until the feedback
signal (FB) oscillates again. Increase
the value until the oscillation ceases.
Then increase further 1.15-1.5 times.
4. Parameter 123 (differentiation time) is
only used in fast systems. The typical
value is the integration time divided
by 4.
5. Reduce control range if necessary
(parameter 120) to reduce over-
shooting.
Note:
The drive should be started / stopped
repeatedly to ensure stability.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 3002 and is the answer not in the manual?

Danfoss VLT 3002 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 3002
CategoryMedia Converter
LanguageEnglish

Related product manuals