EasyManuals Logo
Home>Danfoss>Media Converter>VLT 5000 Crane Series

Danfoss VLT 5000 Crane Series User Manual

Danfoss VLT 5000 Crane Series
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #172 background imageLoading...
Page #172 background image
Pump
A pump is to run at six different speeds, determined by
shifting between the preset references.
Switch no.:
1
3 4
0 0 0 Preset reference 1
0 0 1 Preset reference 2
0 1 0 Preset reference 3
0 1 1 Preset reference 4
1 0 0 Preset reference 5
1 0 1 Preset reference 6
When switch 1 is active, a setup change to setup 2 is
made.
Start/stop by means of switch 2
1. Choice of Setup, lsb
2. Start/stop
3. Preset reference, lsb
4. Preset reference, msb
The following must be programmed in order shown:
Function:
Parameter: Setting: Data value:
Active Setup 004 Multi-Setup [5]
Digital input, term. 16 300 Choice of Setup, lsb [10]
Digital input, term. 32 306 Preset reference, lsb [6]
Digital input, term. 33 307 Preset reference, msb [6]
Setup copying 006 Copy to Setup 2 from # [2]
Edit Setup 005 Setup 1 [1]
Maximum reference 205 60
Preset reference 1 215 10%
Preset reference 2 216 20%
Preset reference 3 217 30%
Preset reference 4 218 40%
Edit Setup 005 Setup 2 [2]
Maximum reference 205 60
Preset reference 5 215 70%
Preset reference 6 216 100%
All other settings are based on factory settings. How-
ever, motor data (nameplate data) must always be
entered in parameters 102-106.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 169
Examples of use

Table of Contents

Other manuals for Danfoss VLT 5000 Crane Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Crane Series and is the answer not in the manual?

Danfoss VLT 5000 Crane Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Crane Series
CategoryMedia Converter
LanguageEnglish

Related product manuals