Function:
This parameter is for setting the DC braking time for
which the DC braking current (parameter 125) is to be
active.
Description of choice:
Set the desired time.
127 DC brake cut-in frequency
(DC BRAKE CUT-IN)
Value:
0.0 - parameter 202
0.0 Hz (OFF)
Function:
This parameter is for setting the DC brake cut-in fre-
quency at which the DC braking current (parameter
125) is to be active, in connection with a stop com-
mand.
Description of choice:
Set the desired frequency.
128 Motor thermal protection
(MOT.THERM PROTEC)
Value:
No protection (NO PROTECTION) [0]
Thermistor warning (THERMISTOR WARN) [1]
Thermistor trip (THERMISTOR TRIP) [2]
ETR Warning 1 (ETR WARNING1) [3]
ETR Trip 1 (ETR TRIP1) [4]
ETR Warning 2 (ETR WARNING2) [5]
ETR Trip 2 (ETR TRIP2) [6]
ETR Warning 3 (ETR WARNING3) [7]
ETR Trip 3 (ETR TRIP3) [8]
ETR Warning 4 (ETR WARNING 4) [9]
ETR Trip 4 (ETR TRIP4) [10]
Function:
The adjustable frequency drive is able to monitor the
motor temperature in two different ways:
-
Via a thermistor sensor connected to one of
the analog inputs, terminals 53 and 54 (pa-
rameters 308 and 311).
-
Calculation of the thermal load, based on the
current load and the time. This is compared
with the rated motor current I
M,N
and the rated
motor frequency f
M,N
. The calculations made
take into account the need for a lower load at
lower speeds because of less cooling from
the fan.
ETR functions 1-4 do not start calculating the load until
there is a switch-over to the Setup in which they were
selected. This enables the use of the ETR function,
even where two or several motors alternate. For the
North American market: The ETR functions provide
class 10 or 20 motor overload protection in accordance
with NEC.
Description of choice:
Select No protection if no warning or tripping is re-
quired when the motor is overloaded.
Select Thermistor warning if a warning is desired when
the connected thermistor - and thus the motor
- gets too hot.
Select Thermistor trip if cutting out (trip) is desired
when the connected thermistor - and thus the motor
- overheats.
Select ETR Warning 1-4, if a warning is to come up on
the display when the motor is overloaded according to
the calculations.
Select ETR Trip 1-4 if tripping is desired when the motor
is overloaded according to the calculations.
The adjustable frequency drive can also be program-
med to give off a warning signal via one of the digital
outputs, in which case the signal is given both for
warning and for trip (thermal warning).
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 97
Programming

Table of Contents

Other manuals for Danfoss VLT 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Series and is the answer not in the manual?

Danfoss VLT 5000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals