VL 5000 Quick Setup
English
Introduction to Quick Setup
This Quick Setup will guide you through EMC correct
installation of the frequency converter by connecting
power, motor and control wiring (fig. 1). Start/stop
ofmotoristobedonewiththeswitch.
For VLT 5122 - 5500 380 - 500 V, VLT 5032 - 5052
200 - 240 V AC and VLT 5075 - 5250 525 - 600 V,
please refer to Technical data and Installation regarding
mechanical and electrical installation.
Fig. 1
1. Mechanical Installation
VLT 5000 frequency converters allow side-by-side mounting. The necessary cooling demands a free air
passage of 1
00 mm above and b elow the frequency converter (5016-5062 380-500 V, 5008-5027 200-240
V and 5016-5062 550-600 V must have 200 mm, 5072-5102, 380-500 V 225 mm).
Drill all holes by using the measurements stated in the table. Please note the difference in unit voltage. Place
the frequency converter on the wall. Tighten up all four screws.
All the below listed measurements are in mm
VLT type A B C a b
Bookstyle IP 20, 200–240 V, (Fig. 2)
5001 - 5003 395 90 260 384 70
5004 - 5006 395 130 260 384 70
Bookstyle IP 20, 380–500 V (Fig. 2)
5001 - 5005 395 90 260 384 70
5006 - 5011 395 130 260 384 70
Com pact IP 54, 20 0–240 V (Fig. 3)
5001 - 5003 460 282 195 260 258
5004 - 5006 530 282 195 330 258
5008 - 5011 810 350 280 560 326
5016 - 5027 940 400 280 690 375
Com pact IP 54, 38 0–500 V (Fig. 3)
5001 - 5005 460 282 195 260 258
5006 - 5011 530 282 195 330 258
5016 - 5027 810 350 280 560 326
5032 - 5062 940 400 280 690 375
5072 - 5102 940 400 360 690 375
Com pact IP 20, 20 0–240 V (Fig. 4)
5001 - 5003 395 220 160 384 200
5004 - 5006 395 220 200 384 200
5008 560 242 260 540 200
5011 - 5016 700 242 260 680 200
5022 - 5027 800 308 296 780 270
Com pact IP 20, 38 0–500 V (Fig. 4)
5001 - 5005 395 220 160 384 200
5006 - 5011 395 220 200 384 200
5016 - 5022 560 242 260 540 200
5027 - 5032 700 242 260 680 200
5042 - 5062 800 308 296 780 270
5072 - 5102 800 370 335 780 330
Fig. 2
Fig. 3
Fig. 4
MG.50.A2.62 - VLT is a registered Danfoss trademark
9

Other manuals for Danfoss VLT 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 and is the answer not in the manual?

Danfoss VLT 5000 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000
CategoryController
LanguageEnglish

Related product manuals