VLT
®
5000 DeviceNet and Allen Bradley Control logix 5550
15
MN.51.T1.02 - VLT is a registered Danfoss trademark
■■
■■
■ Explicit messages with RS Logix 5000
Class Description:
Group 0 = Operation & Display Parameter 001 to 099 Class 100 (64 Hex)
Group 1 = Load & Motor Parameter 101 to 099 Class 101 (65 Hex)
Group 2 = Ref. & Limits Parameter 200 to 299 Class 102 (66 Hex)
Group 3 = Inputs & Outputs Parameter 300 to 399 Class 103 (67 Hex)
Group 4 = Special functions Parameter 400 to 499 Class 104 (68 Hex)
Group 5 = Serial Communication. Parameter 500 to 599 Class 105 (69 Hex)
Group 6 = Technical Function Parameter 600 to 699 Class 106 (6A Hex)
Group 7 = Option Specific Parameter 700 to 799 Class 107 (6B Hex)
Group 8 = DeviceNet Profile Parameter 800 to 899 Class 108 (6C Hex)
Group 9 = DeviceNet Parameter 900 to 999 Class 109 (6D Hex)
Instance Description:
In the Danfoss VLT
5000 we only handle Instance 1,
so always leave this at the value of 1.
Attribute Description:
The attribute for the VLT
5000 parameters is the 2
(two) last digits of the Parameter + 100.
By following this structure all 1 dimensional
parameters can be accessed by Explicit Message.
As example for Parameter 520,
VL VL
VL VL
VL
T 5000 ParameterT 5000 Parameter
T 5000 ParameterT 5000 Parameter
T 5000 Parameter
ClassClass
ClassClass
Class
InstanceInstance
InstanceInstance
Instance
AttributeAttribute
AttributeAttribute
Attribute
520 105 1 120