If a stop command is active via terminal 18 and
the frequency converter is not at the torque limit,
the motor will ramp down to 0 Hz.
If the frequency converter is at the torque limit and
a stop command is activated, terminal 42 Output
(programmed to Torque limit and stop [27]) will be
activated. The signal to terminal 27 will change from
’logic 1’ to ’logic 0’ and the motor will start coasting.
- Start/stop via terminal 18.
Parameter 302 = Start [1].
- Quickstop via terminal 27.
Parameter 304 = Coasting stop, inverse [0].
- Terminal 42 Output
Parameter 319 = Torque limit and stop [27].
- Terminal 01 Relay output
Parameter 323 = Mechanical brake control [32].