Warning:
It can be extremely dangerous to touch the electrical parts
even when the mains supply has been disconnected.
Also ensure that other voltage inputs are disconnected
from load sharing through the DC bus.
Wait at least 4 minutes after the input power has been
removed before servicing the drive.
VLT 2800
175HA490.11
Warning:
Touching the electrical parts may be fatal - even after the equipment
has been disconnected from mains.
Using VLT
6002 - 6005, 200-240 V: Wait at least 4 minutes
Using VLT
6006 - 6062, 200-240 V: Wait at least 15 minutes
Using VLT
6002 - 6005, 380-460 V: Wait at least 4 minutes
Using VLT
6006 - 6072, 380-460 V: Wait at least 15 minutes
Using VLT 6102 - 6352, 380-460 V: Wait at least 20 minutes
Using VLT 6400 - 6550, 380-460 V: Wait at least 15 minutes
Using VLT
6002 - 6006, 525-600 V: Wait at least 4 minutes
Using VLT
6008 - 6027, 525-600 V: Wait at least 15 minutes
Using VLT
6032 - 6275, 525-600 V: Wait at least 30 minutes