EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 302

Danfoss VLT AutomationDrive FC 302 Operating Instructions

Danfoss VLT AutomationDrive FC 302
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
Term.
no.
96 97 98 99
U V W
PE
1
)
Motor voltage 0-100% of mains
voltage.
3 wires out of motor
U1 V1 W1
PE
1
)
Delta-connected
W
2
U2 V2 6 wires out of motor
U1 V1 W1
PE
1
)
Star-connected U2, V2, W2
U2, V2 and W2 to be intercon-
nected separately.
Table 3.14
1)
Protected Earth Connection
NOTICE
In motors without phase insulation paper or other
insulation reinforcement suitable for operation with
voltage supply (such as a frequency converter), fit a Sine-
wave filter on the output of the frequency converter.
U
1
V
1
W
1
175ZA114.11
96 97 98
96 97 98
FC
FC
Motor
Motor
U
2
V
2
W
2
U
1
V
1
W
1
U
2
V
2
W
2
Illustration 3.49 Star/Delta Connections
How to Install
VLT
®
Automation Drive FC 300 Operating Instructions
44 MG33U402 - Rev. 2013-12-16
33

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals