Operation status
Run on ref. The frequency converter is running in the
reference range. The feedback value matches
the setpoint value.
Run request A start command has been given, but the motor
is stopped until a run permissive signal is
received via digital input.
Running The motor is driven by the frequency converter.
Speed high Motor speed is above the value set in
4-53 Warning Speed High.
Speed low Motor speed is below the value set in
4-52 Warning Speed Low.
Standby In Auto On mode, the frequency converter will
start the motor with a start signal from a digital
input or serial communication.
Start delay In 1-71 Start Delay, a delay starting time was set.
A start command is activated and the motor will
start after the start delay time expires.
Start fwd/rev Start forward and start reverse were selected as
functions for two different digital inputs
(parameter group 5-1*). The motor will start in
forward or reverse depending on which
corresponding terminal is activated.
Stop The frequency converter has received a stop
command from the LCP, digital input or serial
communication.
Trip An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, the
frequency converter can be reset manually by
pressing [Reset] or remotely by control
terminals or serial communication.
Trip lock An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, power
must be cycled to the frequency converter. The
frequency converter can then be reset manually
by pressing [Reset] or remotely by control
terminals or serial communication.
Status Messages
VLT
®
AutomationDrive Operating
Instructions
48 MG.33.AJ.02 - VLT
®