The message Empty indicates that no parameters
have been changed.
5.3.6 Restoring Default Settings
NOTICE!
Risk of losing programming and monitoring records by
restoration of default settings. To provide a back-up,
upload data to the LCP before initialisation.
Restoring the default parameter settings is done by initiali-
sation of the frequency converter. Initialisation is carried
out through parameter 14-22 Operation Mode
(recommended) or manually.
Initialisation using parameter 14-22 Operation
Mode does not reset frequency converter settings,
such as operating hours, serial communication
selections, personal menu settings, fault log,
alarm log, and other monitoring functions.
Manual initialisation erases all motor,
programming, localisation, and monitoring data,
and restores factory default settings.
Recommended initialisation procedure, via
parameter 14-22 Operation Mode
1. Press [Main Menu] twice to access parameters.
2. Scroll to parameter 14-22 Operation Mode and
press [OK].
3. Scroll to [2] Initialisation and press [OK].
4. Remove power to the unit and wait for the
display to turn o.
5. Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
6. Alarm 80 is displayed.
7. Press [Reset] to return to operation mode.
Manual initialisation procedure
1. Remove power to the unit and wait for the
display to turn o.
2. Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialisation does not reset the following frequency
converter information:
Parameter 15-00 Operating hours
Parameter 15-03 Power-ups
Parameter 15-04 Over Temps
Parameter 15-05 Over Volts
5.4 Basic Operational Programming
5.4.1
VLT
®
Low Harmonic Drive
Programming
The low harmonic drive includes 2 LCPs: 1 to control the
frequency converter side and 1 to control the lter side.
Because of this unique design, the detailed parameter
information for the product is found in 2 places.
Detailed programming information for the frequency
converter portion can be found in the relevant
programming guide. Detailed programming information for
the lter can be found in the VLT
®
Active Filter AAF 006
Operating Instructions.
The remaining sections in this chapter apply to the
frequency converter side. The active
lter of the low
harmonic drives is pre-congured for optimal performance
and must only be turned on by pressing its [Hand On] key
after the frequency converter side is commissioned.
5.4.2 Commissioning with SmartStart
The SmartStart wizard enables fast conguration of basic
motor and application parameters.
SmartStart starts automatically at rst power-up
or after initialization of the adjustable frequency
drive.
Follow the on-screen instructions to complete the
commissioning of the adjustable frequency drive.
Always reactivate SmartStart by selecting Quick
Menu Q4 - SmartStart.
For commissioning without use of the SmartStart
wizard, refer to chapter 5.4.3 Commissioning via
[Main Menu] or the programming guide.
NOTICE!
Motor data is required for the SmartStart set-up. The
required data is normally available on the motor
nameplate.
Start-up and Functional Tes...
VLT
®
AutomationDrive FC 302 Low Harmonic Drive
132–630 kW
56 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A322
55

Table of Contents

Other manuals for Danfoss VLT CANopen MCA 105

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CANopen MCA 105 and is the answer not in the manual?

Danfoss VLT CANopen MCA 105 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CANopen MCA 105
CategoryDC Drives
LanguageEnglish

Related product manuals