5 The triangle indicates if the LCP is in Status, Quick Menu, or Main Menu.
B. Menu key
Press [Menu] to select among Status, Quick Menu, or Main Menu.
C. Navigation keys and indicator lights
Table 13: Legend to Section C
6 Com. LED: Flashes during bus communication.
7 Green LED/On: Control section is working correctly.
8 Yellow LED/Warn.: Indicates a warning.
9 Flashing Red LED/Alarm: Indicates an alarm.
10 [Back]: For moving to the previous step or layer in the navigation structure.
11 [▵] [▿] [▹]: For navigating among parameter groups and parameters, and within parameters. They can also be used for setting
local reference.
12 [OK]: For selecting a parameter and for accepting changes to parameter settings.
D. Operation keys and indicator lights
Table 14: Legend to Section D
13 [Hand On]: Starts the motor and enables control of the drive via the LCP (disabled on 18.5–22 kW (22–30 hp)).
NOTICE
[2] Coast inverse
is the default option for
parameter 5-12 Terminal 27 Digital Input
. If there is no 24 V supply to
terminal 27, [Hand On] does not start the motor. Connect terminal 12 to terminal 27.
14 [Off/Reset]: Stops the motor (Off). If in alarm mode, the alarm is reset.
15 [Auto On]: The drive is controlled either via control terminals or serial communication.