6.5.8 Digital Outputs
Number of digital outputs 4
Terminals 27 and 29
Terminal number
27, 29
(1)
Voltage level at digital output 0–24 V
Maximum output current (sink and source) 40 mA
Terminals 42 and 45
Terminal number
42, 45
(2)
Voltage level at digital output 17 V
Maximum output current at digital output 20 mA
The load resistor at digital output 1 kΩ
1
Terminals 27 and 29 can also be programmed as input.
2
Terminals 42 and 45 can also be programmed as analog output.
The digital outputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
6.5.9 Control Card, RS485 Serial Communication
Terminal number 68 (P, TX+, RX+), 69 (N, TX-, RX-)
Terminal number 61 common for terminals 68 and 69
6.5.10 Control Card, 24 V DC Output
Terminal number 12
Maximum load 80 mA
6.5.11 Relay Outputs, Enclosure Sizes H3–H5
Programmable relay output 2
Relay 01 and 02, enclosure sizes H3–H5 01–03 (NC), 01–02 (NO), 04–06 (NC), 04–05 (NO)
Maximum terminal load (AC-1)
(1)
on 01–02/04–05 (NO) (Resistive load)
250 V AC, 3 A
Maximum terminal load (AC-15)
(1)
on 01–02/04–05 (NO) (Inductive load @ cosφ 0.4)
250 V AC, 0.2 A
Maximum terminal load (DC-1)
(1)
on 01–02/04–05 (NO) (Resistive load)
30 V DC, 2 A
Maximum terminal load (DC-13)
(1)
on 01–02/04–05 (NO) (Inductive load)
24 V DC, 0.1 A
Maximum terminal load (AC-1)
(1)
on 01–03/04–06 (NC) (Resistive load)
250 V AC, 3 A
Maximum terminal load (AC-15)
(1)
on 01–03/04–06 (NC) (Inductive load @ cosφ 0.4)
250 V AC, 0.2 A
Maximum terminal load (DC-1)
(1)
on 01–03/04–06 (NC) (Resistive load)
30 V DC, 2 A
Minimum terminal load on 01–03 (NC), 01–02 (NO) 24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1 Overvoltage category III/pollution degree 2
1
IEC 60947 parts 4 and 5. Endurance of the relay varies with different load type, switching current, ambient temperature, driving configuration, working profile, and so forth. Mount a
snubber circuit when connecting inductive loads to the relays.
Specifications
Operating Guide | VLT® Compressor Drive CDS 803
AQ321748767627en-000101 / 130R0570
48 | Danfoss A/S © 2019.12

Other manuals for Danfoss VLT CDS 803

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 803 and is the answer not in the manual?

Danfoss VLT CDS 803 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 803
CategoryDC Drives
LanguageEnglish

Related product manuals