Page #175 background imageLoading...
Page #175 background image
Model
525–550 V
551–690 V
N250
101
70
92
64
N315
118
84
108
77
N355
151
112
138
102
N400
191
135
175
125
N500
134
90
123
83
N560
154
119
141
109
N630
173
154
173
141
N710
208
155
190
142
N800
282
208
258
190
11.6.3 Non-fusible Disconnect Losses
Table 139: Power Losses for Non-fusible Disconnect Option, 380–480 V (Losses Shown in Watts)
Model
380–440 V
441–480 V
NO
HO
NO
HO
N110
8
6
7
5
N132
13
8
11
7
N160
19
13
17
11
N200
29
19
25
17
N250
44
29
37
25
N315
65
44
54
37
N355
25
21
20
17
N400
32
25
26
20
N450
36
27
30
26
N500
43
36
34
30
N560
55
43
44
34
Table 140: Power Losses for Non-fusible Disconnect Option, 525–690 V (Losses Shown in Watts)
Model
525–550 V
551–690 V
NO
HO
NO
HO
N110
4
2
3
2
N132
5
4
5
3
N160
8
5
7
5
N200
12
8
11
7
N250
17
12
16
11
AQ357954340588en-000201 / 130R0881 | 175Danfoss A/S © 2020.09
Appendix
VLT® Refrigeration Drive FC 103
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 302 N450 and is the answer not in the manual?

Danfoss VLT FC 302 N450 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 302 N450
CategoryDC Drives
LanguageEnglish

Related product manuals