MCD 200 Design Guide
14 MG.17.C3.02 – VLT is a registered Danfoss trademark
MCD 201
Description of choice:
Set the ramp time to optimise stopping characteristics
for the load.
■ Indication
LED OFF ON FLASH
Ready No control
power
Ready Starter
tripped
Run Motor not
running
Motor
running at
full speed
Motor
starting or
stopping
■ Fault Finding
Ready LED Description
x 1
Power Circuit Fault:
Check mains supply L1, L2 & L3,
motor circuit T1, T2 & T3 and soft
starter SCRs.
x 6
Supply Frequency:
Check supply frequency is in range
x 8
Network Comms Failure (between
accessory module and network):
Check network connections and
settings.
x 9
Starter Comms Failure (between starter
and accessory module): Remove and
refit accessory module.