- 3 -
Input Point
Input No. X0 ~ X3
#1
X4 ~ X7 X10 ~ X17, X20 ~
#2
Input type Digital input
Input form DC (SINK or SOURCE)
Input current 24VDC, 5mA
Input impedance 4.7KΩ
Max. frequency 100kHz 10kHz 60Hz
Action level
Off On >15VDC
On Off < 5VDC
Response time
Off On < 2.5μs < 20μs < 10ms
On Off < 5μs < 50μs < 15ms
Filter time X0 ~ X7 Adjustable within 0 ~ 20ms in D1020 (Default: 10ms)
Output Point
Output point type Relay-R Transistor-T
Output point number All Y0, Y2 Y1, Y3 Y4 ~ Y17, Y20 ~
#2
Voltage specification < 250VAC, 30VDC 5 ~ 30VDC
#3
Max. frequency 1Hz 100kHz 10kHz 1kHz
Leakage current - <100uA
Maximum load
Resistive 2A/1 point (5A/COM) 0.5A/1 point (4A/COM)
#5
Inductive
#4
15W (30VDC)
Lamp 20WDC/100WAC 2.5W(30VDC)
Minimum load 1mA / 5V
Response time
Off On
Approx .10ms
< 2μs < 20μs < 100μs
On Off < 3μs < 30μs < 100μs
#1: The counting frequency of X1 and X3 on the DVP-ES200 series PLCs and the DVP-EX200
series PLCs which are produced after 2013 is increased from 10 kHz to 100 kHz.
#2: Please refer to “I/O Terminal Layout” for the max. X/Y No. on each model.
#3: UP, ZP must work with external auxiliary power supply 24VDC (-15% ~ +20%), rated
consumption approx. 1mA/point.
#4: The lifetime of IO relays may differ depending on operating voltage, load type (power factor
cosø, time constant t) and different contact current. The number of operations during the
lifetime can be estimated by means of the following chart of life curves.
Contact
Current(A)
20
0.5
0.1
0.2
30
50
0.3 0.7 1 2
200
300
500
100
1,000
2,000
3,000
O
p
e
r
a
t
i
o
n
(
X
1
0
)
3
120VAC Resistive
30VDC Inductive(t=7ms)
240VAC Inductive(cos 0.4)
ψ
=
120VAC Inductive(cos =0.4)
ψ
30VDC
Inductive
( t=40ms )
[ Figure 3 ]
#5: ZP for NPN COM, UP for PNP COM.
A/D and D/A Specifications (For EX2 Model Only)
Items
Analog Input (A/D) Analog Output (D/A)
Voltage Current Voltage Current
Analog I/O range ±10V ±20mA 4 ~ 20mA
#1
±10V 0 ~ 20mA 4 ~ 20mA
#1
Digital conversion
range
±2,000 ±2,000 0 ~ +2,000 ±2,000 0 ~ +4,000 0 ~ +4,000
Resolution
#2
12-bit
Input impedance > 1MΩ 250Ω -
Output impedance - 0.5Ω 1MΩ
Tolerance carried
impedance
- 5KΩ 500Ω
Overall accuracy
Non-linear accuracy: ±1% of full scale within the range of PLC operation
temperature
Maximum deviation: 1% of full scale at 20mA and +10V
Response time 2ms (set up in D1118)
#3
2ms
#4
Absolute input
range
±15V ±32mA -
Digital data format
2s complement of 16-bit, 12 significant bits