Delta DVP-ES2 Instruction Sheet

Delta DVP-ES2
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
- 2 -
Model
name
16ES2
00R/T
24ES2
00R/T
32ES2
00R/T
40ES2
00R/T
40ES2
00RM
58ES2
00R/T
60ES2
00R/T
80ES2
00R/T
20EX2
00R/T
32ES2
11T
L 105 125 145 165 165 225 225
302
145 145
L1 97 117 137 157 157 217 217
294
137 137
WT
R
377g 414g 489g 554g 562g 705g 696g 890g 462g
T 351g 387g 432g 498g 622g 614g 785g 442g 321g
Model
name
20ES2
00RE/
TE
32ES2
00RE/
TE
40ES2
00RE/
TE
60ES2
00RE/
TE
L 125 165 194 255
L1 117 157 186 247
WT
RE 453g 569g 630g 787g
TE 416g 520g 574g 704g
Electrical Specifications
Model
Item
32ES211T All ES2 models except for 32ES211T
Power supply
voltage
24VDC(-15~+20%) 100 ~ 240VAC (-15% ~ 10%); 50 / 60Hz 5%
Connector European standard removable terminal block (Pin pitch: 5mm)
Operation
ES
200
DVP-ES2 starts to run when the power rises to 95 ~ 100VAC and stops
when the power drops to 70VAC. If the power is suddenly cut off, the PLC
will continue running for 10ms.
ES
211
DVP-ES2 starts to run when the power rises to 20.4VDC~28.8VDC and
stops when the power drops to 17.5VDC. If the power is suddenly cut off,
the PLC will continue running for 10ms.
Power supply
fuse
2.5A / 30VDC, Polyswitch 2A / 250VAC
Power
1.8W 30VA
DC24V current
output*1
500mA
Power supply
DC24V output short circuit protection
Voltage
withstand
1,500VAC (Primary-secondary), 1,500VAC (Primary-PE),
500VAC (Secondary-PE)
Insulation
> 5MΩ at 500VDC (between all I/O points and ground)
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV, Analog &
Communication I/O: 1kV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Grounding
The diameter of grounding wire shall not be less than that of L, N terminal of
the power supply. (When many PLCs are in use at the same time, please
make sure every PLC is properly grounded.)
Environment
Operation: 0°C~55°C (temperature), 5~95% (humidity), pollution degree 2
Storage: -25°C~70°C (temperature), 5~95% (humidity)
Agency
approvals
UL508, European community EMC Directive 89/336/EEC and Low Voltage
Directive 73/23/EEC
Vibration/shock
immunity
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 &
IEC 68-2-27 (TEST Ea)
*1: It is suggested that the power output should not be supplied to HMIs.