MC • Edition 2023.04 • No. 298 073 Re. -0
6 … 16
7 … 16
6. Technical data for MPA 41xx
Protection class MPA 4112, MPA 4114 IP 54
External display IP 54 front / IP 20 rear
Protection class MPA 4122 IP 65
Ambient temperature -40 °C...+70 °C
Storage and transport -40 °C...+80 °C
Humidity DIN 60730-1, no dewing admissible
Operating altitude Suitable for use up to 2 000 metres above
mean sea level
Service life of switching outputs At least 250 000 switching operations
Installation position Any
Dimensions MPA 411x in mm MPA 4112 / 4114 (L x H x D): approx.
152.5 x 165 x 77 mm
Weight MPA 411x 0.82 kg
Dimensions MPA 412x in mm
MPA 4122 (L x H x D): approx. 160 x 240 x
100 mm
Weight MPA 412x 2.2 kg
7. Electrical data for MPA 41xx
Rated voltage 230 VAC -15% ... +10% or 115 VAC -15%
... +10%
Frequency 50 Hz ... 60 Hz
Fuse 6.3 A delayed or 10 A fast-acting,
integrated, replaceable
Isolation No galvanic isolation between grid and
24 VDC or 5 VDC
Electrical connection In-phase connection and protective earth
connection according to connection
diagram
The touch protection for the UV sensor
must be ensured through installation in
the operating equipment
Power consumption (own consumption) Maximum 10 W
Short-circuit current ION against N 115 / 230 VAC 280 µA
Outputs
Designation
Safety-
relevant
Output type Line
length
Electrical data
V1 / V2
Gas valves
•
Relay contact 100 m
115 / 230 VAC / 2 A cos φ = 1 / minimum load
0.5 W
Ignition • Electr. relay 100 m 115 / 230 VAC / 2 A cos φ = 1*
Fan Relay contact 100 m 115 / 230 VAC / 1 A cos φ = 0.4 corresponds
to 115 / 230VAC / 2.5 A cos φ = 1
Operation / fault Relay contact 100 m 115 / 230 VAC / 1 A cos φ = 1
Supply
Flame detector
100 m 230 VAC / 10 mA (also version MPA 115 VAC)
*1 With a pre-ignition time > 100 s or a duty cycle (DC) > 80 % of the ignition output, the maximum permissible
output current is reduced to 1.5 A.
The total currents of all safety-related consumers must not exceed 5 A (note the safety value)
The total currents of all consumers must not exceed 6.3 A (10 A).
Inputs
Designation Input type Line length Electrical data
Safety chain Potential-free contact 100 m 115 / 230 VAC / max. 5 A
Flame detector 1 (ionisation) Ionisation 10 m Threshold: approx. 1.2 μA
X 16 to X 20
e.g. remote unlocking, air pressure
monitor, heat request, ame detector 2
Switching contact 100 m 115 / 230 VAC
AM 41 display connetion - 10 m internal
Use ame detector 2 for line lengths > 10 m.
For special applications, ionisation line lengths of up to 50 m are possible on request.
Dierent functions can be parameterised for inputs X 16 to X 20, see chapter tbd.
Safety devices in the safety chain must have potential-free normally open or normally closed contacts suitable
for mains voltage and at least 10 A current load.
The connection lines must be suitable for an ambient temperature of at least 75 °C.
8. Inputs / outputs