1. Brief introduction
--4--
1.4 Product specification and performance
General specification
Model 10000HXL31 15000HXL31 20000HXL31
Power Rating 10KVA/7KW 15KVA/10.5KW 20KVA/14KW
Frequency (Hz) 50/60Hz 50/60Hz 50/60Hz
Voltage (304-478)VAC (304-478)VAC (304-478)VAC
Input
Current 50A max. 75A max. 100A max.
Voltage 240VDC 240VDC 240VDC
Battery
Current 40A max 60A max 80A max
Voltage 220VAC 220VAC 220VAC
Output
Current 45A 68A 91A
Dimension (WxDxH) mm 260x570x717 260x570x717 260x570x717
Weight (kg) 39 55 55
Electrical performance
Input
model Voltage Frequency Power Factor
10000/15000/20000 Three-phase(380VAC/220VAC) 46-54Hz/56-64Hz
>0.95(Full
load)
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion Overload capacity
Current
crest ratio
±1%
0.7 lag
Synchronized
50/60HZ(±4Hz) in
Line mode (AC
mode)
±0.1% of normal
frequency in
Battery mode
THD<2%
Full load
(Linear
Load)
105%-130% load transfers to
bypass mode after 10
minutes
>130% load transfers to
bypass mode after 1 second
and shutdown the output after
1 minute
3:1
maximum
Operating environment
Temperature Humidity Altitude Storage temperature
0°C-40°C
<95% <1000m
0°C--40°
Note: if the UPS is installed or used in a place where the altitude is above than 1000m,
the output power must be derated in use, please refer to the following :
Altitude(M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating power 100% 95% 91% 86% 82% 78% 74% 70% 67%