EasyManuals Logo
Home>Eaton>UPS>5PX

Eaton 5PX User Manual

Eaton 5PX
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
614-40095-00
40
8.5 Electrical output
All models Normal mode Battery mode
Voltage regulation
Boost : Vin*1.15
Buck : Vin*0.87
(-10% ,6%)
Efficiency >96%
1000-2200 > 82%
3000 > 85%
Frequency regulation +/-0.1 Hz
Nominal output
100/110/120/125V
Frequency Follows input frequency 50/60Hz
Output overload
[105%,120%] 30min
[120%,150%]5min
>150% 10S
[105% ~110%] 10s
[110%~150%]1s,
>150% 0.15s
Short circuit current limitationin battery
mode
Model
Current
limitation
1000 41A
1500 56A
2000 66A
3000 90A
Transfer time
Utility Outage: 1-4ms for normal mode, >5ms for sensitive mode
Utility abnormal: <10ms for normal mode ,<25ms for sensitive mode
8.6 Electrical output connection
Catalog Number
Output conection
5PX1000RTG2
5PX1000RTNG2
(4) 5-15R Primary
(2) 5-15R Group1
(2) 5-15R Group2
5PX1500RTG2
5PX1500RTNG2
5PX2000RTG2
5PX2000RTNG2
5PX2000RT3UNG2
(2)5-20R + (1)L5-20R Primary
(2) 5-20R Group1
(2) 5-20R Group2
5PX3000RTG2
5PX3000RTNG2