Eaton Cutter-Hammer SPB-50 User Manual

Eaton Cutter-Hammer SPB-50
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
I
.
B
.
29
-
801
C
Page
12
the
application
requirements
.
For
maintenance
and
/
or
safety
requirements
,
a
push
-
to
-
open
padlockable
adapter
is
available
to
hold
the
breaker
in
the
OPEN
position
(
Section
5
-
10
)
.
4
-
1.5
HOW
TO
DISCHARGE
STORED
ENERGY
WITHOUT
CLOSING
BREAKER
As
a
safety
feature
,
it
is
possible
to
locally
discharge
the
breaker
s
stored
energy
without
closing
the
breaker
.
This
is
possible
in
both
manually
and
electrically
operat
-
ed
breakers
.
Control
power
to
the
electrical
operator
must
be
removed
to
prevent
undesired
recharging
.
The
action
involved
in
releasing
the
stored
energy
without
closing
the
main
contacts
causes
an
abnormally
high
shock
condition
on
the
breaker
and
should
be
avoided
except
for
emergency
reasons
.
To
release
this
stored
energy
when
the
breaker
is
in
the
OPEN
position
:
First
,
depress
and
hold
the
PUSH
-
TO
-
OPEN
pushbut
-
ton
and
then
depress
the
PUSH
-
TO
-
CLOSE
pushbut
-
ton
.
When
the
breaker
is
in
the
CLOSED
and
CHARGED
position
,
the
above
actions
will
simultaneously
open
the
breaker
and
discharge
the
stored
energy
.
Figure
4
-
2
Indexing
Bracket
Shown
in
TEST
Position
(
Breaker
Removed
for
Clarity
)
JBk
WAHNiNU
4
-
1.3
HOW
TO
CLOSE
SHOULD
THE
LOCAL
PUSH
-
TO
-
CLOSE
BUTTON
BE
ACCIDENTALLY
DEPRESSED
WITH
THE
BREAKER
IN
THE
CLOSED
POSITION
AND
WITH
THE
MECHANISM
CHARGED
,
THE
ENERGY
WILL
BE
RELEASED
AND
THE
BREAKER
COULD
SHOCK
OPEN
.
THEREFORE
,
CARE
SHOULD
BE
EXERCISED
TO
AVOID
THIS
OPERATION
.
All
that
is
required
to
close
the
breaker
locally
is
to
push
the
mechanical
PUSH
-
TO
-
CLOSE
pushbutton
.
Precharged
breakers
may
be
closed
remotely
via
a
spring
release
solenoid
which
is
standard
for
electrically
operated
breakers
and
optional
for
manually
operated
breakers
(
Section
5
-
3
)
.
For
special
applications
,
local
manual
closing
may
not
be
desired
.
Provisions
are
available
in
the
form
of
a
manual
closing
blocking
adapter
to
prevent
this
action
except
by
authorized
per
-
sonnel
(
Section
5
-
11
)
.
THE
STORED
ENERGY
CANNOT
BE
DISCHARGED
WITHOUT
CLOSING
THE
BREAKER
FROM
A
REMOTE
LOCATION
.
Before
attempting
to
close
the
breaker
locally
,
the
yel
-
low
stored
energy
window
must
read
CHARGED
.
Electrical
interlocks
are
provided
to
prevent
remote
clos
-
ing
unless
the
closing
energy
is
fully
charged
and
the
mechanism
is
ready
to
be
closed
.
4
-
2
DRAWOUT
MECHANISM
Movement
of
the
breaker
on
its
drawout
is
easily
accomplished
by
using
the
drawout
indexing
lever
and
ratchet
crank
,
with
one
exception
as
described
in
Section
4
-
2.1
.
The
indexing
lever
must
always
be
lifted
before
any
drawout
movement
is
begun
,
and
it
must
be
held
until
the
indexing
lever
block
clears
the
slot
for
the
position
being
vacated
.
Complete
instructions
are
given
for
racking
the
breaker
in
and
out
of
the
cell
using
the
drawout
mechanism
on
NP
235
P
001
H
01
attached
to
the
rear
of
the
cell
door
(
Figures
4
-
2
and
4
-
3
)
.
4
-
1.4
HOW
TO
OPEN
Opening
the
breaker
locally
is
accomplished
with
the
mechanical
PUSH
-
TO
-
OPEN
pushbutton
on
the
breaker
control
faceplate
.
Breakers
may
be
opened
remotely
via
either
a
shunt
trip
device
(
Section
5
-
2
)
or
an
undervoltage
release
(
Section
5
-
6
)
,
depending
upon
F
:
T
*
N
Effective
7
/
00
Courtesy of NationalSwitchgear.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Cutter-Hammer SPB-50 and is the answer not in the manual?

Eaton Cutter-Hammer SPB-50 Specifications

General IconGeneral
BrandEaton
ModelCutter-Hammer SPB-50
CategoryCircuit breakers
LanguageEnglish

Related product manuals