3-8.3 MECHANICAL ACCESSORIES
There are eight optional mechanical type accessories:
Operations Counter
Off Key Lock
Cassette Lock
Pushbutton Cover
Prevent Close Cover
Cassette Safety Shutters
Cassette Cell Switch
Door Escutcheon
Waterproof Cover
Mechanical Interlock
Operations Counter - The operations counter is a
mechanical device used to provide a record of the num-
ber of circuit operations. It is mounted in the lower right
portion of the circuit breaker and can be viewed through
the front cover (Figure 3-57).
Off Key Lock - The off key lock secures the circuit
breaker in the “OFF” position. It is mounted in the lower
right portion of the circuit breaker and can be viewed
through the front cover (Figure 3-57). The customer
supplies the key lock. The provisions available are for
Kirk, Castell or Ronis.
Cassette Lock - A cassette mounted lock can be used
in conjunction with different interlocking schemes (such
as main-tie-main) (Figure 3-58). The lock holds the cir-
cuit breaker trip-free in the connected position, prevent-
ing it from being closed.
Up to three lock cylinders can be installed on one cas-
sette. Cutler-Hammer supplies the lock provisions only.
The customer is responsible for the locks, which can be
Kirk or Castell.
Pushbutton Cover - Padlockable covers are available
to limit access to the “ON” and “OFF” pushbuttons
(Figure 3-59). They can be installed with either or both
pushbutton covers in place.
Prevent Close Cover - All access to the “ON” pushbut-
ton can be prevented by adding the fixed Prevent Close
Cover to the pushbutton cover.
Lockout Cover - When padlocked, it maintains the
“OFF” button in the actuated position which prevents
closure of the breaker.
Figure 3-57 Cover Mounted Key Lock and Operations
Counter
Operations
Counter
“OFF”
Key Lock
Figure 3-58 Cassette Mounted Key Lock
Figure 3-59 ON-OFF Pushbutton Lockable Cover Plate
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton MDS-816 and is the answer not in the manual?

Eaton MDS-816 Specifications

General IconGeneral
BrandEaton
ModelMDS-816
CategoryPower Tool
LanguageEnglish

Related product manuals