SOFTWARE FEATURES
Notifications:
Inlet thermistor disconnected
Heating enabled based on default
parameters and history data.
Check thermistor connections. Check
parameter P000 and adjust if needed.
Outlet thermistor disconnected
Heating enabled without calibration.
Check outlet thermistor connection.
Inlet AND outlet thermistors
disconnected
Heating enabled based on default
parameters and history data.
Check thermistor connections. Check
parameter P000 and adjust if needed.
Current transformer disconnected
Heating enabled based on default
parameters. Limited self-diagnostic
capabilities.
Check current transformer connections.
Channel 1 element outside
tolerance, LOW kW rating
Unit runs as intended, attempting to
compensate.
Channel 2 element outside
tolerance, LOW kW rating
Channel 3 element outside
tolerance, LOW kW rating
Channel 1 element outside
tolerance, LOW kW rating
Heating disabled on the associated
channel.
Channel 2 element outside
tolerance, LOW kW rating
Channel 3 element outside
tolerance, LOW kW rating
Heating disabled on the associated
channel.
Check element(s). Check SSR connections.
Check contactor.
Check for tripped ECOs. Check elements.
Check SSR connections. Check contactor.
Inlet temperature 180-200F
Heating disabled while condition is
present.
Check water supply temperature.
Inlet temperature above 200F
Heating disabled. Heating resumes after
condition disappears, with a delay.
Inlet temperature higher than
setpoint
Outlet temperature too high (>20F
above setpoint)
Heating disabled while condition is
present.
Check elements. Check incoming voltage.
Check SSRs functionality.
Inlet or outlet temperature too low
Unit runs as intended. Heating not
disabled. Unit freezing and damage
possible.
Check water supply temperature. Verify
installation location temperature to be
above freezing point.
Unit runs as intended. Heating not
disabled.
Consider upgrading the unit or reducing
flow.