C6 Max set point range +85°C. To limit the maximum set point
C5 Min set point range -50°C To limit the minimum set point
A7 Alarm delay range 0-60 minutes. Delay before alarm activates
C7 Compressor short cycle protection range 0-90 minutes. Stops
compressor stop starting excessively
A2 Compressor run time in event of probe failure range 0-60 minutes.
Compressor will run for this timed period with no input to avoid thawing
of product
A3 Compressor stop time in event of probe failure range 0-60 minutes.
Compressor will cycle off after this period of time with no input to avoid
freezing product
D1 Evaporator probe presence 0 = disabled 1 = enabled
D2 Probe calibration range -10 to 10°C adjustment of probe input reading
if accuracy is poor due to extended probe or interference
D7 defrost stop temperature, defrost terminates when this setting is
reached
F5 fan stop temperature, fans will not run at or above this setting
D8 drip time, at end of defrost time is allowed for condensate to drip off
coil
D11 defrost mode 0 is electric heater 1 is hot gas
F1 fan mode 0 fan operates simultaneously with compressor 1 fan
operates continuously stops during defrost 2 fan operates continuously
stops during defrost and drip time 3 fan operates continuously stops
during defrost fan time delay after defrost 4 Controlled by sensor fan stops
during defrost
A full list of parameters follows (some are optional and depend on model)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Elitech ECS-2180neo and is the answer not in the manual?

Elitech ECS-2180neo Specifications

Operating Environment IconOperating Environment
operating temperature-5 to 55°C
storage temperature-10 to 65°C
temperature range-40 to 90°C
Power IconPower
power supply12/24 Volt DC
power consumption< 10 watts
Outputs IconOutputs
compressor output current17/7 Amp
fan output current10 Amp
defrost output current10 Amp
Weight and Dimensions IconWeight and Dimensions
front panel dimensions34.5 (H) x 76mm (W) +/- 2mm
cut out dimensions30 (H) x 72mm (W) +/- 1mm

Related product manuals