EasyManuals Logo
Home>Emerson>Controller>EC3-D72

Emerson EC3-D72 User Manual

Emerson EC3-D72
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background image
Operating instruction
EC3-D7x Digital Superheat Controller
EC3-D72 with TCP/IP communication capability
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 18.07.2017 EC3-D7x_OI_ML_R06_865019.docx
General information:
EC3-D72 is the superheat controller with TCP/IP connection for stepper motor
driven Electrical Control Valves EX4-6 from EMERSON and is optimized to operate
with the Copeland Digital Scroll series utilizing a 0-10V input from a third-party
controller. The controller synchronizes the PWM digital compressor solenoid valve
with the superheat controlled by the electrical control valve; EX series.
The EC3-D73 has the same functionality but can only be set-up via the ECD-002
display. It has no external communication functionality.
Safety instructions:
Read operating instructions thoroughly. Failure to comply can result in device
failure, system damage or personal injury.
According to EN 13313 it is intended for use by persons having the
appropriate knowledge and skill.
Do not exceed the specified maximum ratings for pressure, temperature,
voltage and current.
Before installation or service disconnect all voltages from system and device.
Do not operate system before all cable connections are completed.
Entire electrical connections have to comply with local regulations.
Note: The EC3-D7x series contains a VRLA battery = valve regulated rechargeable
lead-acid battery. The battery must NOT be disposed of with other commercial waste.
Instead, it is the user’s responsibility to pass it to a designated collection point for the
safe recycling of batteries (harmonized directive 2012/19/EU). For further
information contact your local environmental recycling center.
Mounting position:
The EC3-D7x is designed to be mounted onto a standard DIN rail. Mounting
position: on vertical walls, with stepper motor connector on top side only.
Mounting of ECD-002:
ECD-002 can be installed at any time also during operation.
ECD-002 can be mounted in panels with
71x29 mm cutout.
Push controller into panel cut-out.(1)
Make sure that mounting lugs are flush with
outside of controller housing
Insert Allen key into front panel holes and turn
clockwise. Mounting lugs will turn and gradually
move towards panel (2)
Turn Allen key until mounting lug barely touches
panel. Then move other mounting lug to the same
position (3)
Tighten both sides very carefully until keypad is
secured. Do not over tighten as mounting lugs
will break easily.
Electrical Installation:
Refer to the electrical wiring diagram for electrical connections.
Do not apply voltage to the controller before completion of wiring.
Ground the metal housing with a 6.3 mm spade connector.
Keep controller and sensor wiring well separated from mains wiring. Minimum
recommended distance 30 mm.
Use a class II category transformer for 24 VAC power supply. Do not ground the
24 VAC lines. We recommend using individual transformers for EC3 controller(s)
and for 3
rd
party controllers to avoid possible interference or grounding problems
in the power supply. Connecting any EC3 inputs to mains voltage will permanently
damage the EC3.
The use of the relay is essential to protect the system in case of power failure if the
communications interface or the ECD-002 are not utilized.
If the output relay is not utilized, the user must ensure appropriate safety pre-
cautions are in place to protect the system against damage caused by a power
failure.
In order to provide system protection in the event of power loss, it is recommended
to change the battery annually.
Digital input status is dependent to operation of compressor/0-10V input
System
Operating
condition
Digital Inputs
0-10V input from third party
controller
C1 &
C2 in stop mode
“Cooling demand” open (0 V)
“Comp 2 Running” open (0 V)
EXV remains closed irrespective
of voltage input value
C1 in run &
C2 in stop mode
“Cooling demand” closed (24
V)
“Comp 2 Running” open (0
V)
EXV active
Input = 0V: dig. valve capacity =
10% default capacity.
If dig. comp. is in by-pass,
EXV will:
- close if capacity is <70%
- be inhibited if capacity is
>70%
C1 &
C2 in run mode
“Cooling demand” closed (24 V)
“Comp 2 Running” closed (24
V)
EXV active
EXV always modulates
even when
the dig. compr. is in by-pass mode.
C1 in stop &
C2 starts run
mode
“Cooling demand” open (0 V)
“Comp
2 Running” closed (24 V)
EXV remains closed irrespective
of voltage input value
Note 1: C1 = Compressor 1, C2 = Compressor 2
Note 2: Digital comp. should always be regarded as base load compressor 1.
Wiring:
A: White wire
B: Black wire
C: Blue wire
D: Brown wire
E: M12 Plug cable assembly EXV-Mxx for connection to EX4-6
F: 24 V Triac output to PWM Digital Scroll valve
G: Remote control panel, system controller.
H: Alarm relay, dry contact. Relay coil is not energized at alarm or power off.
I: Digital input “Cooling demand” (0 V/open = Stop; 24 V/closed = Start)
J: Transformer Class II, 24 VAC secondary / 25 VA
K: Third party controller (can use the analog output signal from EC3)
L: Pump down relay, dry contact. Relay is energized during normal operation
M: Digital input 2: “Comp 2 running”
(0 V/ open = Comp 2 stop; 24 V /closed = Comp. 2 running)
N: Discharge Temp. Sensor Copeland® NTC
O: 0-10 V Digital Scroll capacity demand signal from system controller
P: ECN-N60 Temperature sensor
!

Other manuals for Emerson EC3-D72

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson EC3-D72 and is the answer not in the manual?

Emerson EC3-D72 Specifications

General IconGeneral
BrandEmerson
ModelEC3-D72
CategoryController
LanguageEnglish

Related product manuals