SHOULD YOU ENCOUNTER ANY PROBLEMS
INSTALLING THIS UNIT, CALL US ON:
1
Safety
Read and understand these instructions before beginning
installation. The unit should be installed by a competent person.
Location
Check there is space for the unit in your chosen location. The unit
must not affect the operation of open-flue appliances. Consult local
regulations or a qualified gas engineer. For inline units consider the
external vent location in relation to open-flues from appliances e.g.
boilers. You must ensure the vent is positioned a minimum of 300mm
away in all directions.
The open sides of the diffuser must face a minimum 1m unobstructed
path away from any smoke detectors. If the diffuser cannot be
repositioned, up to two sides can be closed using the plastic blanking
plates. In this configuration the open sides must face a minimum
1.5m unobstructed path away from any smoke detectors. If using the
100mm diffusers, no blanking plates are supplied and the diffusers
must be repositioned.
In properties with a floor above 4.5m fire diffusers must be fitted
a minimum of 1m away from the smoke detectors instead of the
included plastic diffusers.
Partition walls between buildings must be complete with any
breaks filled.
In properties with a floor more than 4.5m above ground level the unit
must be wired into a smoke alarm (see page 16 for wiring information).
The appliance is considered suitable for use in countries with a warm
damp equable climate, but may also be used in other countries.