EasyManuals Logo
Home>Friedrich>Thermostat>EMWRT2

Friedrich EMWRT2 User Manual

Friedrich EMWRT2
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
42
22 – AUTOMATIC HUMIDITY CONTROL
00 Disable automatic humidity control;
01 * Enable automatic humidity control;
When “Automatic Humidity Control” is enabled
, thermostat will turn on
air conditioning in an unoccupied room when humidity raises above
60% and room temperature is above 72°F until either room humidity
is below 55% or room temperature is below 72°F
;
* Indicates default setting;
This setting is active only on thermostats with enabled humidity
features. Changing this setting on a non-humidity thermostat will have
no effect on thermostat operation.
Humidity features can be enabled on compatible thermostats via
online management.
Certain models only. Additional fees apply.
Custom Energy Savings Settings

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Friedrich EMWRT2 and is the answer not in the manual?

Friedrich EMWRT2 Specifications

General IconGeneral
BrandFriedrich
ModelEMWRT2
CategoryThermostat
LanguageEnglish

Related product manuals