EasyManuals Logo
Home>Fujitsu>Air Conditioner>ABHG36KRTA

Fujitsu ABHG36KRTA User Manual

Fujitsu ABHG36KRTA
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #127 background imageLoading...
Page #127 background image
6-1. Defrost operation in heating operation stopped
If the outdoor unit is frosted when stopping the heating operation, it stops after performing the auto-
matic defrosting operation.
In this time, if the indoor unit operation lamp flashes slowly (6 sec on/2 sec off), the outdoor unit al-
low the heat exchanger to defrost, and then stop.
Triggering condition
When all of the following conditions are satisfied in heating operation
Compressor operation integrating time: 30 minutes or more
Compressor continuous operation time: 10 minutes or more
Outdoor unit heat exchanger temperature: -4°C or less
Release condition
The defrost operation is released when either one of the conditions below is satisfied.
Outdoor unit heat exchanger temperature
(after 1 minute or later since compressor start)
12°C or more
Compressor operation time 15 minutes
6-1. Defrost operation in heating operation stopped - (04-21) - 6. Defrost operation control