EasyManuals Logo

Fujitsu Airstage VR-II ARUV30TLAV User Manual

Fujitsu Airstage VR-II ARUV30TLAV
246 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #184 background imageLoading...
Page #184 background image
If the amount of recovered refrigerant is available that was pulled out of outdoor unit which compressor
was replaced.
(When the refrigerant is recovered by refrigerant recovery machine, and its weight is measured.)
If the amount of recovered refrigerant from outdoor unit that compressor was replaced is not sure.
(When the refrigerant leakage was the case.)
>>> Once recover all units' refrigerant, and recharge the calculated amount of refrigerant (Original
amount and additional amount) again after vacuuming.
Note: To use the recovered refrigerant is not recommended in case of refrigerant leakage.
Always charge fresh refrigerant with correct amount for the system after repairing.
>>> Perform vacuuming of repaired outdoor unit thoroughly, and add the refrigerant with the recovered
amount.
2. Refrigerant charging after the compressor replacement.
Connect the high pressure service port of the broken master unit and the low pressure pipe of the broken
master unit by pressure gauge.
>>> Refrigerant release from the heat exchanger of the broken master unit.
(Refrigerant is removed until refrigerant shortage is resolved)
<How to respond, when refrigerant is deficient>
Reuse the refrigerant of the broken master unit.
Broken
master unit
Substitutional
master unit
Slave
unit #1
All 3 Way-Valves Close
Open and adjust
High pressure (service port)
Liquid
Hp Gas
Lp Gas
Recover the remaining refrigerant in the broken master unit from the service port(s).
2
When new refrigerant is added to the operating system, check the weight of additional refrigerant,and
adjust the total refrigerant amout after repairing.
04-94

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage VR-II ARUV30TLAV and is the answer not in the manual?

Fujitsu Airstage VR-II ARUV30TLAV Specifications

General IconGeneral
BrandFujitsu
ModelAirstage VR-II ARUV30TLAV
CategoryAir Conditioner
LanguageEnglish

Related product manuals