When function setting is "Forced stop" mode
In the case of "Edge" input
Function
setting /
Rotary SW of
External input and
output PCB
External input Input signal Command
46-02
- Input of indoor unit Terminal
Off → On Forced stop
On → Off Normal
60-00 / 1
External input and
output PCB
Input 1
Off → On Forced stop
On → Off Normal
On
Off
Forced stop
Normal
Operation
Stop
Remote controller
On On
Indoor unit
On
Input
In the case of "Pulse" input
Function
setting /
Rotary SW of
External input and
output PCB
External input Input signal Command
46-02 60-00 / 1
External input and
output PCB
Input 1 Pulse Forced stop
Input 2 Pulse Normal
On
Off
Operation
Stop
Remote controller
On
Off
Forced stop
Normal
Input 1
Input 2
On On On
Indoor unit
NOTES:
When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the re-
mote controller is restricted.
When forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
- 44 -
8-4. Details of function 8. External input and output
CEILING TYPE
ABYG18-45KRTA
CEILING TYPE
ABYG18-45KRTA

Table of Contents

Other manuals for Fujitsu ARXG22KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG22KMLA and is the answer not in the manual?

Fujitsu ARXG22KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG22KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals