EasyManuals Logo
Home>Fujitsu>Air Conditioner>ARXG22KMLA

Fujitsu ARXG22KMLA Design & Technical Manual

Fujitsu ARXG22KMLA
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
10. Function settings
To adjust the functions of this product according to the installation environment, various types of
function settings are available.
NOTE:
Incorrect settings can cause a product malfunction.
10-1. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting proce-
dure and the content of each function setting, select appropriate functions for your installation envi-
ronment.
¢
Setting procedure by using remote controller
Remote controller is not attached for this product. For details of the installing remote controller, refer
to following information.
Overview information: Operating manual of the remote controller
Setting procedure: Installation manual of the remote controller
¢
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no. Functions
1) 11 Filter sign
2) 20 Ceiling height
3) 28 Horizontal louver direction switching for dew condensation prevention
4) 30/31 Room temperature control for indoor unit sensor
5) 35/36 Room temperature control for wired remote controller sensor
6) 40 Auto restart
7) 42 Room temperature sensor switching
8) 44 Remote controller custom code
9) 46 External input control
10) 48 Room temperature sensor switching (Aux.)
11) 49 Indoor unit fan control for energy saving for cooling
12) 60 Switching functions for external output terminal
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number Setting value Setting description Factory setting
11
00 Standard (2,500 hours)
01 Long interval (4,400 hours)
02 Short interval (1,250 hours)
03 No indication
- 50 -
10-1. Function settings by using remote controller 10. Function settings
CEILING TYPE
ABYG18-45KRTA
CEILING TYPE
ABYG18-45KRTA

Table of Contents

Other manuals for Fujitsu ARXG22KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG22KMLA and is the answer not in the manual?

Fujitsu ARXG22KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG22KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals